Guided Relays; Input Devices; Magnetic Switches - Pepperl+Fuchs FYQLA1-140R-3 Instruction Manual

Door interrupt system with logic amplifier
Table of Contents

Advertisement

Door Interrupt System with FYQLA1-140R-3 Logic Amplifier

Guided relays

The door interrupt system incorporates two force-guided safety relays that are
monitored for proper operation and generate a redundant output for application
use.

Input devices

Magnetic switches

The 50FY41 series hall effect door switches are a noncontact, magnetic actuation
system consisting of a sensor and a magnetically keyed actuator. The sensor
contains two hall-effect integrated circuits that are connected independently.
When exposed to this magnetic actuator and properly aligned, the sensor
responds with an output.
Approved devices
Attention
NOTE: These are the only approved devices that should be used.
50FY41 sensor alignment
Attention
Cable length
Attention
12
50FY41 series
52FY31 series
Ensure the alignment of the sensor and magnetic actuator are correct
for proper operation. A 10 mm (0.39 in) separation distance between
sensor and actuator will cause an OFF condition, independent of axial
offset distance.
Sensor cable length must not exceed 25 m (80 ft).
Hall effect door interrupt sensor
Keyed hall effect magnetic-actuator