Connecting Profinet - Siemens SIMATIC PN/BACnet LINK Operating Instructions Manual

Network transitions
Table of Contents

Advertisement

7.5

Connecting PROFINET

Connecting PROFINET
PROFINET connection
Connecting PROFINET
Note
To increase the mechanical stability, optimized retaining collars
connectors are installed on the bottom part of the housing of the PN/BACnet LINK in the
delivery state. These retaining collars are intended for the Siemens FastConnect connectors.
NOTICE
Make sure you observe the minimum bending radius of the Ethernet cable; otherwise the
shield effect of the cable shield may be impaired. There is also the risk that the cable shield
breaks.
NOTICE
EMC stability is only guaranteed with shielded PROFINET cables.
PN/BACnet LINK
Operating Instructions, 10/2017, A5E39895543-AA
7.5 Connecting PROFINET
Connect Ethernet cable according to PROFINET
specification to higher-level controller and / or the
next PROFINET node
Use a shielded Ethernet cable with shielded con-
nector for the connection.
We recommend RJ45 connectors from the Sie-
mens FastConnect system as connectors for the
Ethernet cabling.
Always apply the shields of the PROFINET
Ethernet cable at both ends.
for the two Ethernet
Connecting
.
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents