Siemens SIMATIC PN/BACnet LINK Operating Instructions Manual page 78

Network transitions
Table of Contents

Advertisement

Diagnostics
10.1 Status LEDs
RUN LED
Flashes
Flashes
Flashes
1) The MAINT LED currently has no meaning.
x: LED state is irrelevant
During boot-up of the PN/BACnet LINK and after connecting the power supply, the sequence
is as follows:
1. The three LEDs light up briefly for about 1 second and then go dark again.
2. None of the LEDs light up for about 4 seconds.
3. The RUN LED starts flashing.
4. When the run-up of the PN/BACnet LINK is successfully complete and the connection to
the S7 controller is established, the RUN LED lights up.
78
ERROR
MAINT
LED
LED
On
On
On
Off
Off
Off
Off
Off
x
On
Off
x
Off
Flashes
Off
Off
Off
Flashes
Operating
state
1)
Power-up test / Seri-
ous error
System run-up
Not connected to S7
controller
Connected to S7
controller
Error state
Firmware update
LEDs are flashing
(triggered by
TIA Portal)
Operating Instructions, 10/2017, A5E39895543-AA
Description
For approximately 1 second: LED
test during startup
Longer than 1 second: HW error
detected during power-up test or
other serious error
System not completely booted yet
but power-up test is complete.
No "IO controller" connection estab-
lished or
configuration not yet completed.
"IO controller" connection estab-
lished and configuration completed.
"IO controller" connection estab-
lished and configuration completed,
but an error occurred:
Diagnostic message to the S7
controller is pending or
Incorrect configuration by the S7
controller
Flashes for at least 3 seconds.
While the firmware is written to the
flash memory.
3-second intervals
For identification of the device
PN/BACnet LINK