Eaton Cutler-Hammer Digitrip RMS 510 Instructions Manual page 49

Application ol retrolit kits on power circuit breakers
Hide thumbs Also See for Cutler-Hammer Digitrip RMS 510:
Table of Contents

Advertisement

AD
33-855-4
Page 48
9.2
Information Available
to Operator
While Breaker ls in Service
Table
9-1 lists the available information provided
by Digitrip RMS
Trip Units while
the Breaker is
in
service.
Table
9-1
Data
available
local
to, or remote
from,
the
Digitrip
RMS Trip
Unit during operation.
RMS
510
RMS
otu
BMS
810
RMS
910
Unit Status Green
LED
flashes
to indicate
normal
operation
of
Trip
Unit.
X
X
X
X
Long Delay Red
LED
flashes
when
Breaker is
in
Long Delay Pickup and
timing
out
to trip.
X
X
X
X
High Load Red
LED
lights when
current
level
stays
within 85% of
Long Delay Pickup for 40 seconds.
X
X
X
ATR
High Load
contact
closes
for
remote
indication
when current level stays
within 85% of
Long Delay
Pickup for 40 seconds.
X
X
X
Alphanumeric
Digital
Display,
showing:
LDPU
(Flashing)
when Breaker in
Long
Delay Pickup;
lndividual
Phase
Cunents
(reading
in
amps
x
1000);
Ground Current (reading
in
amps
x
1000);
Peak Demand
(Mega
Watts);
Present Demand (Mega Watts);
Energy
(Mega
Watt
Hours).
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Depress STEP
push-button to
view selected
field.
X
X
X
Depress
RESET
push-button to
reset peak demand.
X
X
Communications
Data
Available
for
remote
use
at
master
PC,
including:
Trip
Unit
PowerNet
Address
(set at
Trip
Unit);
Breaker Status (open or closed);
Reason for Status (normal, LDPU alarm, or other);
Breaker Rating Plug lnstalled;
High Load lndication;
lndividual
Phase
Current levels
(amps);
Ground Current levels
(amPs);
Peak Demand
(Mega
Watts);
Present Demand (Mega Watts);
Energy
(Mega
Watt Hours);
Power
Factor;
Power Quality (Harmonics);
Voltage.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ElT.t
Efiective 9/01

Hide quick links: