Ipm Over Current Error (Error Code : E464) - Samsung AC026RN1DKG Service Manual

System air conditioner single for europe (r32, heat pump)
Hide thumbs Also See for AC026RN1DKG:
Table of Contents

Advertisement

Troubleshooting

4-3-17 IPM over current error (Error Code : E464)

1. Test items
1) Check the power connection. / Check the restart after power reset.
2) Install outdoor unit and check environment.
→ Check for wire disconnection related to outdoor unit Inverter PCB and check the installation environment.
→ After having installed several units, please check that communication wires are not interchanged with piping.
3) Check the indoor unit installation environment.
4) Check the opening of service valve.
5) Check the status of compressor assembly and wiring.
6) Check the defective for compressor wire single parts.
2. Check procedure
Power on 30 seconds after power off.
Is the outdoor unit installed properly?
Is the indoor unit installed properly?
Is indoor and outdoor unit wiring/piping
installed properly?
Continue
4-42
Yes
Yes
Yes
Outdoor unit installation and environment
check. → Check for normal operation at
restart. → End the service.
1. Check for wire disconnection related to
No
outdoor
unit Inverter PCB.
2. Remove obstacle on the inlet of outdoor
unit and secure the space.
Check installation environment of indoor
unit. → check for normal operation at restart.
→ End the service.
No
1. Remove obstacle on the inlet and secure
the space.
2. Remove obstacle on the outlet and secure
the space.
No
Install again by following the standard
Piping
Wiring
specifications.
Bad installation