Page 3
GENERAL INFORMATION..............................27 8.1.2 PROBLEMS WITHOUT ERROR INDICATION ON DISPLAY ....................27 8.1.3 TABLE ALARMS REPORTED TO DISPLAY - VERSION I - ....................... 28 NOTES AND INFORMATION SERVICE .............................. 29 NOTE ....................................... 29 Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 3...
It is forbidden to disperse and leave within reach of children of the' packing material as it can be potentially dangerous. • Observe the safety distances between the machine and other equipment or structures to ensure a sufficient drive access space for maintenance and service operations as described in this booklet. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 4...
It warns that failure to observe the precaution may cause damage to the unit or system. It warns that there is the presence of moving parts and involves a risk of damage to DANGER exposed persons Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 5...
Installations carried out outside of the warnings of this manual or use outside of the operating limits will void instantly check the warranty. Make sure that the first operation is carried out by authorized personnel from 'company (see form required initial startup) Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 6...
The excision, the deterioration and the illegibility of the nameplate on the unit, involves great problems in the identification of the machine, in the availability of spare parts, and then in all its future maintenance. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx...
Thanks to the special construction and its components the unit is able to achieve recovery efficiency greater than 90% .In the winter and summer seasons there is a considerable energy recovery of air introduced into the environment renewal. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 8...
If there are no channels installed on one of the aeraulic 4 outlets, provide adequate protection to install a network. Check the power supply and the grounding of the unit. 1.1.12 REMOVAL AND DISPOSAL Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 9...
Page 10
Do not disassemble or dispose of the product yourself. The disassembly, demolition, disposal of the product must be performed by authorized personnel in accordance with local regulations. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 10...
The simultaneous operation of the unit and a natural draft boiler (eg. Open fireplace) may cause a depression in the environment, which may occur due to a backflow of exhaust gas into the environment. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 11...
Not mount the unit with the hips in direct contact with the walls to avoid possible noises from contact, insert strips of rubber or neoprene in this case. Wall mounting Bracket for wall mounting Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 12...
For the correct connection of the air ducts, refer to the following diagram and the places adhesives unit. Table diameters links Aerodynamic units Size 20 H 20 V 30 H 30 V 40 H 40 V 50 H 50 V Ø mm Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 13...
Page 14
According to the plant in which the unit must be installed, it will be possible to suitably orient the four aeraulici attacks. Below any possible configurations: CONFIGURATION VERSION HORIZONTAL H CONFIGURATION VERSION HORIZONTAL V UNITS 'VIEWS ARE LISTED ABOVE AND MUST BE ORDERED WITH THE DESIRED CONFIGURATION Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 14...
-Verify after the first moments of operation the tightening of the screws of the power terminals Table for the dimensioning of the power line Size 20 H 20 V 30 H 30 V 40 H 40 V 50 H 50 V Maximum current 0.74 0.74 absorbed Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 15...
N - CL - CP Water valve / battery post Contact voltage (220v) REMOTE DISPLAY Remote control (4-wire) ON OFF remote contact present on the remote ON OFF REMOTE (ON DISPLAY) Contact closed / unit OFF display Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 16...
The card allows the operation of the brushless EC fan through a remote command described above; They have been implemented in some auxiliary functions such as the tab connecting the controllers and the management of a battery / post valve; Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 17...
Page 18
/ off remote unit such as a switch or a timer The logic includes: Contact closed: unit OFF Contact open: Unit ON Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 18...
Page 19
The connection is made on terminals GRID as indicated on the circuit diagram Connecting Regulator humidity Note: You can connect both the air quality regulator is the humidity regulator in parallel on the same terminals; Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 19...
Page 20
LINK GENERATOR / POST OF BATTERY The unit provides the command of a generator or a battery post, through the clean contact terminal; Contact closed with active request; Link generator / battery post Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 20...
(eg. 18 ° C); Electric battery The battery in any case must be installed with the lid upwards in order to avoid malfunctions of the safety devices. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 21...
WORKING VERSION -I- The unit is completely manually controlled way by the user, through the touch command to CNV wall; there is the possibility of connecting the sensors humidity regulator and air quality; switch 3V Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 22...
Page 23
-Pressing the auto key, the unit will operate at rated speed taking active control of the input sensors; If the humidity controller or air quality, require it, the unit will increase the speed, the speed sensors; The input is a digital input to connect a clean contact; AUTO Function Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 23...
Page 24
With Ignition is off hold down the + button for 5 seconds until the written 01. With the button - set the value to 00 and wait 20 seconds to verify the correct setting. Dimming setting time slots Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 24...
For cleaning, it is possible to use a vacuum cleaner, a rag moistened with water, a soft-bristled brush or a low-pressure compressor. Warning! On the blades are small metal clip for balancing the blades, DO NOT remove them. Views units for general cleaning Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 26...
-Voltage of too low difficult start -Food the unit with partially closed shutters so as to reduce -Pair insufficient motor the engine torque. In case of departure correct, replace the motor with a plus. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 27...
Page 28
The LED indicates the presence of power on LINK alarm the card; Hours of operation reached for dirty filter Check the the on off button to reset the report of dirty filter alarm (default = 0) the filter and hold; Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 28...
Page 32
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 09 20 17 Re v. 09 Technical Assistance Center The data contained herein may be modified by the manufacturer without notice. Innova S.r.l. N420231A_ManualHRP DOMO_ Rev9.EN.docx Pag. 32...
Need help?
Do you have a question about the HRP DOMO and is the answer not in the manual?