ABB RELION 630 Series Product Manual page 6

Generator protection and control
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Generator Protection and Control
REG630
Product version: 1.3
3I
3I
3U
Io
Uo
3U
EXC.
AVR
3I
3I
REK510
U
fn
Io
Io
Uo
GUID-42A3A43D-4F62-4541-AB39-D662B21769AB V1 EN
Figure 3.
Medium-sized generator in block connection with a transformer
The protection is implemented with two REG630 generator
protection relays and one REF630 feeder terminal. One
REG630 is taking care of protecting the generator itself, the
second REG630 is protecting the power transformer with
6
REF630
U
Preconf.
12
ANSI
IEC
25
SYNC
27/47U+
3U</U1<
46
I2>
50N/51N
Io>>>
50P/51P
3I>>>
51BF/51NBF
3I>/Io>BF
51P-1/51P-2
3I>/3I>>
59/47O-
3U>/U2>
59G
Uo>
60
FUSEF
67N-1/67N-2
Io>→/Io>>→
68
3I2f>
REG630
Preconf.
ANSI
IEC
32R/32O
P>→
40
X<
46G/46M
I2>G/M
51BF/51NBF
3I>/Io>BF
51N-1/51N-2
Io>/Io>>
51P-1/51P-2
3I>/3I>>
59
3U>
59G
Uo>
81U/81R
f</df/dt
87T
3ΔI>T
REG630
Preconf.
ANSI
IEC
21GT
Z<GT
24
U/f>
27
3U<
27/59THD
ΔU
>/Uo>
03f
32R/32O
P>→
49T/G
3Ith>T/G
51BF/51NBF
3I>/Io>BF
51P-1/51P-2
3I>/3I>>
59
3U>
59G
Uo>
60
FUSEF
64R
Io>R
n
n
n
available transformer differential protection function and
REF630 is protecting and controlling the feeder part of this
application.
1MRS757583 C
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg630

Table of Contents