Table 24. Electromagnetic compatibility tests, continued
Description
Voltage dips and short interruptions
Electromagnetic emission tests
• Conducted, RF-emission (mains terminal)
0.15...0.50 MHz
0.5...30 MHz
• Radiated RF-emission
30...230 MHz
230...1000 MHz
Table 25. Insulation tests
Description
Dielectric tests
• Test voltage
Impulse voltage test
• Test voltage
Insulation resistance measurements
• Isolation resistance
Protective bonding resistance
• Resistance
Table 26. Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
24
Type test value
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
<79 dB(µV) quasi peak
<66 dB(µV) average
<73 dB(µV) quasi peak
<60 dB(µV) average
<40 dB(µV/m) quasi peak, measured at 10 m
distance
<47 dB(µV/m) quasi peak, measured at 10 m
distance
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
>100 MΩ, 500 V DC
<0.1Ω, 4 A, 60 s
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3 (method A)
1MRS757583 C
Reference
IEC 61000-4-11
EN 55011, class A
IEC 60255-25
Reference
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27
IEC 60255-27
Requirement
Class 1
Class 1
Class 1