ABB RELION 630 Series Product Manual page 16

Generator protection and control
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Generator Protection and Control
REG630
Product version: 1.3
IEC 60870-5-103 is available from optical serial port where it is
possible to use serial glass fibre (ST connector) or serial plastic
fibre (snap-in connector).
The protection relay supports the following time
synchronization methods with a timestamping resolution of 1
ms.
Ethernet communication based
• SNTP (simple network time protocol)
• DNP3
Table 6. Supported communication interface and protocol alternatives
1)
Interfaces/protocols
IEC 61850
DNP3
IEC 60870-5-103
● = Supported
1)
Please refer to the Selection and ordering data chapter for more information
16
Ethernet
100BASE-TX RJ-45
With special time synchronization wiring
• IRIG-B (Inter-Range Instrumentation Group - Time Code
Format B)
IEC 60870-5-103 serial communication has a time-stamping
resolution of 10 ms.
Ethernet
100BASE-FX LC
Serial snap-in
1MRS757583 C
Serial ST
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg630

Table of Contents