5.7

Setting vitality

i
5.7.1

Connecting a CS11 (and FC700A) directly to the MK8000

Building Technologies
Fire Safety & Security Products
The vitality timer defines the maximum time between telegrams received from the
subsystem. Recommended vitality is 50 seconds (maximum 90 seconds). Setting
the vitality is recommended when using GW20 or GW21. It is mandatory when
connecting a CS11 directly to the MK8000.
Note: Setting the vitality timer is mandatory when connecting a CS11 directly to
MK8000, while it needs to be '0' when a CS11 is connected via MK7022 to the
MK8000.
When connected directly to the MK8000, CS11 AlgoRex and FC700A require su-
pervision by the vitality check. You set the vitality timer in the Node tab of the CK11
(and FG700A) and the CC11 (and FC700A).
Connecting a CS11/FC700A to the MK8000
To connect a CS11/FC700A to MK8000, do the following:
1. Set the Vitality (in seconds) in the subsystem node tab for the CK11(FG700A)
and CC11(FC700A). See Fig 39.
2. Drag the CK11(FG700A) to the MK8000 Cerloop Driver.
Fig 39
Setting the vitality check in the CC11 directly connected to the MK8000