Commissioning & Adjustments
9
The heating curve is limited at the upper end by maximum flow temperature ("MAX TEMP")
Maximum Flow Temperature
To limit the heating curve at the upper end
"MAX TEMP" adjustable from 25 - 80˚C
Factory setting 80˚C

Room Influence Factor

If the actual room temperature deviates too much from the set room temperature, the set flow
temperature can be raised by a factor per 1 K deviation.
The higher the value for "ROOM INFLUENCE", the greater the increase in the set flow temperature.
"ROOM INFLUENCE" adjustable from 0 - 10
Delivered condition 0

Heating Limit

Heating mode ends when the set outside temperature ("HEATING OFF AT") is reached.
"HEATING OFF AT" adjustable from 15 - 25˚C
Delivered condition - -
Settings for Room Temperature-Dependent Mode ("ROOM CONTROL")
Depending on the set and actual room temperatures, the required flow temperature is determined
and transmitted to the control unit of the heat generator.
Maximum Flow Temperature
To limit the maximum flow temperature.
"MAX TEMP" adjustable from 25 - 80˚C
Factory setting 80˚C