Siemens SIMATIC NET CP 443-1 Advanced Manual page 85

S7-400 - industrial ethernet
Hide thumbs Also See for SIMATIC NET CP 443-1 Advanced:
Table of Contents

Advertisement

Exceptions / restrictions:
● Write access is permitted only for the following MIB objects of the system group:
– sysContact
– sysLocation
– sysName
For all other MIB objects / MIB object groups, only read access is possible for security
reasons.
● Traps are not supported by the CP.
"Interfaces" MIB group
The "Interfaces" MIB object provides status information on the CP interfaces, with the
following assignment:
This group returns status information about the CP interfaces. The MIB objects of the ifTable
provide the status information of the interfaces. The "ifIndex" object identifier is assigned to
the CP interfaces as follows:
Table 6- 1
ifIndex
ifIndex
1
*)
2-5 (1-4)
*)
6 (5)
*)
*) If the gigabit interface is not configured, the value 1 is assigned to the first port of the PROFINET interface; the next
values then move accordingly by one position.
Access permissions using community name
The CP uses the following community names to control the access rights in the SNMP
agent:
Table 6- 2
Access rights in the SNMP agent
Type of access
Read access
Read and write access
*) Note the use of lowercase letters!
MIB file and SNMP profile file
You will find the MIB file and the SNMP profile file of the module in the STEP 7 installation in
the folders "S7DATA" > "snmp" under the name of the module.
CP 443-1 Advanced (GX30)
Manual, 03/2019, C79000-G8976-C256-05
A set sysName is sent as the host name using DHCP option 12 to the DHCP server to
register with a DNS server.
Type of interface
Gigabit interface
Port 1-4 (PROFINET interface)
Internal CP interface
Community name
*)
public
private
Configuration and operation
6.12 SNMP
85