Siemens SIMATIC NET CP 443-1 Advanced Manual page 17

S7-400 - industrial ethernet
Hide thumbs Also See for SIMATIC NET CP 443-1 Advanced:
Table of Contents

Advertisement

● Open communication services with the following functions:
– SEND/RECEIVE interface over ISO transport connections
– SEND/RECEIVE interface over TCP connections, ISO-on-TCP and UDP connections
– Multicast over UDP connection
– FETCH/WRITE services (server services; corresponding to S5 protocol) via ISO
– LOCK/UNLOCK with FETCH/WRITE services (CPU-dependent; see section
● Open TCP/IP communication
Open TCP/IP communication provides a program interface for the transfer of connection-
oriented and connectionless services. The establishment and termination of connections
is initiated here only via the "dynamic" program interface.
STEP 7 provides a UDT for the connection description as well as four FBs for data
exchange.
The CP supports communication via ISO-on-TCP connections for this interface.
● SIMATIC Safety - Fail-safe communication
The CP supports fail-safe communication via S7 connections. A fail-safe connection can
run from the local CPU via the CP to the relevant communications partner, for example
another F-CPU or a fail-safe distributed I/O system.
You do not need to configure any special safety relevant properties for the CP.
● IT functions
– HTTP
– Web server: Monitoring devices and process data (HTML process control)
– FTP
– E-mail
CP 443-1 Advanced (GX30)
Manual, 03/2019, C79000-G8976-C256-05
With the SEND/RECEIVE interface via TCP connections, the CP supports the socket
interface to TCP/IP available on practically every end system.
UDP frame buffering on the CP can be disabled during configuration. When
necessary, this allows you to achieve a shorter reaction time between the arrival of a
UDP frame and its evaluation on the CPU.
The multicast mode is made possible by selecting a suitable IP address when
configuring connections.
transport connections, ISO-on-TCP connections and TCP connections;
Here, the SIMATIC S7400 with the CP is always the server (passive connection
establishment) while the read or write access (client function with active connection
establishment) is always initiated by a SIMATIC S5 or a device from another range /
PC.
Requirements for use (Page 41))
FTP functions (File Transfer Protocol) for file management and access to data blocks
in the CPU (client and server functions)
Sending e-mail via SMTP or ESMTP. The CP supports t SMTP-Auth for authentication
on an email server and STARTTLS.
Properties and services
1.3 Communication services
17

Hide quick links:

Advertisement

Table of Contents
loading