IFM Electronic Ecomot300 AC2630 Device Manual page 28

Field modules dp
Hide thumbs Also See for Ecomot300 AC2630:
Table of Contents

Advertisement

Field modules DP
Process data
The analogue input module processes signals from 0/4���20 mA with a resolution of
16 bits�
Adjustment of the measuring values at 0���20 mA
Process data
hex
decimal
0000
0
3FFF
16383
7FFF
32767
Adjustment of the measuring values at 4���20 mA
Process data
hex
decimal
0000
0
3FFF
16383
7FFF
32767
Data representation is according to the integer number format (INT)� The process
data are entered in the default settings in the two's complement format (-1
corresponds to 0xFFFF)�
28
Measured value
0 mA
10 mA
20 mA
Measured value
4 mA
12 mA
20 mA