Check that the gas is turned off.
Center the burner on the fireplace floor.
The burner should be located under the
flue opening.
The grate should be placed over the
burner so the front legs of the grate are
just in front of the burner pipe. The back
legs goes into the slots in the back plate
of the burner.
Remove the grate and proceed with the

gas connection.

NOTE- if the floor is recessed or
glass doors are installed, burner
must be elevated with firebrick or
equivalent to ensure proper air flow
over valve systems.
Check that the gas is turned off. Any
remote kits should be installed on the
burner at this point, refer to instructions
with kit for that installation.
The gas supply line should be ½"
inside diameter (ID) up to 30 feet and
¾" for longer distance.
Use the non-whistling flex connector
provided in the accessory kit to
connect the gas supply to the burner
kit. Check to make sure the burner is
in the correct position.
Turn the gas supply on and check
connection for leaks using a soapy
solution.
NOTE- at this point install and
program any remote kits, refer to
the
instructions
those kits for installation.
BURNER AND GRATE POSITIONING
GAS CONNECTION
provided
with
BURNER POSITION
IMPORTANT:
The minimum inlet supply pressure for
the purpose of input adjustment is 5.0 inches (natural
gas) 11 inches (propane gas) in water column.
maximum inlet supply pressure is 10.5 inches (natural
gas) 13 inches (propane gas) in water column.
Connect to gas
The
6