6.1.3 Fiber Optic Connections

When making connections to the transmitter and receiver inputs/outputs, ensure that the transmit output from one
device is connected to the receive input of the next device. Figure 6-1 shows how to insert the connector. The tip of
the cable on the ST connector must be clean and free of dust. Dust on the tip of the cable will cause signal
attenuation.
Caution: Use extreme care when handling the fiber optic connector, especially the exposed ceramic ferrule.

6.2 RS-485 Twisted-pair Cable

The following sections provide the information necessary to select and install cable between an MJ-X Control
Panel, RTU, and other field devices in an RS-485 network.

6.2.1 RS-485 Cable Type

Listed in Table 6-1 are the cable characteristics necessary for proper electrical performance in an RS-485
communications network. Use cable with a shield that provides 100 percent RFI/EMI coverage.
Characteristic
Impedance
Capacitance (pF/ft)
Cable Size
DC Resistance
Velocity of Propagation

6.2.2 RS-485 Cable Grounding

Ground the cable shield for all devices on the network. Ground the cable shield at only one end to prevent induced
interference that may result from circulating ground currents. If a cable shield is grounded at both ends a ground
loop can exist between the components. This ground loop can cause induced interference that results in signal
distortion. If there is a ground potential rise between the connected devices, connect the Signal Return (RTN)
between the communication devices. Figure 6-2 illustrates the preferred field device connection method. See section
3.1.2 on page 7 for jumper considerations.

Figure 6-1 Fiber Optic Connections

Table 6-1 RS-485 Cable Specifications
Value
120 ohms
35
22 AWG
17 ohms/1000 ft
80%
MJ-X Communications Module
Maximum/Typical
Typical
Maximum
Typical
Maximum
Maximum