ABB REJ 513 User Manual page 55

Overcurrent relay
Table of Contents

Advertisement

ABB Substation Automation
Products and Systems
1MRS750613-MUM
User's Guide
Table 2.2.2-7 Power outputs (PO1 and PO2)
• Rated voltage
• Continuous carry
• Make and carry for 3.0 s
• Make and carry for 0.5 s
• Breaking capacity when the control circuit time-
constant L/R < 40 ms, at 48/110/220 V dc
• Minimum contact load
Table 2.2.2-8 Enclosure class
Front side
Rear side, connection
terminals
Note!
A rear protective cover (accessory part) can be used to protect and shield the rear
of the case.
Table 2.2.2-9 Environmental tests
• Specified service
temperature range
• Transport and storage
temperature range
• Dry heat test
• Dry cold test
• Damp heat test, cyclic
250 V ac/dc
5 A
15 A
30 A
5 A / 3 A / 1 A
100 mA at 24 V ac/dc
IP 54 (flush-mounted)
IP20
-10...+55 °C
-40...+70 °C
according to IEC 60068-2-2
according to IEC 60068-2-1
according to IEC 60068-2-30
REJ 513
55