ABB REJ 513 User Manual page 41

Overcurrent relay
Table of Contents

Advertisement

ABB Substation Automation
Products and Systems
1MRS750613-MUM
User's Guide
Settings
Table 2.1.7.3-1 Settings
Variable
Start current of stage I>
Operate time or time
multiplier k of stage I>
Start current of stage I>>
Operate time of stage
I>>
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGB 1
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Operate time of circuit-
breaker failure protection
1)
Values above 1 equal 1.
2)
If the protection stage has been set out of function, "999" displaces the number
indicating the currently used value in serial communication.
Actual
Group 1
settings
(R, W, P)
(R)
S1
S41
S2
S42
2)
S3
S43
S4
S44
S5
S45
S6
S46
S7
S47
S8
S48
S9
S49
S10
S50
S11
S51
S12
S52
-
S121
REJ 513
Group 2
Setting
(R, W, P)
range
S81
0.30...5.00 x I
S82
0.05...300 s /
0.05...1.00
S83
0.30...35.0 x I
S84
0.04...300 s
S85
0...255
S86
0...255
S87
0...255
S88
0...255
S89
0...255
S90
0...255
S91
0...255
S92
0...255
S121
0.10...1.00 s
n
1)
n
41

Advertisement

Table of Contents
loading

Table of Contents