Operation indicators

The function of the relay can be monitored with the help of three indication LEDs on
the relay front panel.
Network Partner
REJ 513
READY
START
TRIP
C
Order
No: REJ513A 402-BAA
Uaux = 110-240 Vac
Software
No: 1MRS118012
Uaux = 48-220 Vdc
Serial
No: ER 000001
fn
= 50/60 Hz
In = 1/5 A (I)
Figure 1-1 Operation indicators
Green READY indicator
• Indicator off:
The auxiliary voltage supply to the relay has been disconnected.
• Lit indicator:
The relay is in normal operation, i.e. the CPU operates, no internal faults have
occurred, and auxiliary voltage is available to the relay.
• Blinking indicator:
The internal self-supervision system has detected an internal relay fault (IRF). The
output contact of the self-supervision system operates.
REJ 513