After installation is completed, the following method must be used to determine if the exhaust system is acceptable:
1. Connect an inclined or digital manometer between the dryer and the point the exhaust connects to the dryer.
2. Set the dryer timer and temperature to air fluff (cool down) and start the dryer.
3. Read the measurement on the manometer.
4.The system back pressure MUST NOT be higher than 0.75 inches of water column. If the system back pressure is less
than 0.75 inches of water column, the system is acceptable. If the manometer reading is higher than 0.75 inches of water
column, the system is too restrictive and the installation is unacceptable.
Although vertical orientation of the exhaust system is acceptable, certain extenuating circumstances could affect the
performance of the dryer:
1. Only the rigid metal duct work should be used.
2. Venting vertical through a roof may expose the exhaust system to down drafts causing an increase in vent restriction.
3. Running the exhaust system through an uninsulated area may cause condensation and faster accumulation of lint.
4. Compression or crimping of the exhaust system will cause an increase in vent restriction.
The exhaust system should be inspected and cleaned a minimum of every 18 months with normal usage. The more the
dryer is used, the more often you should check the exhaust system and vent hood for proper operation.
C
L

Location of your dryer

Do not install your dryer:
In an area exposed to dripping water or outside water conditions.
In an area where it will come in contact with curtains drapes, or anything that will obstruct of combustion and
ventilation air.
On carpet, floor must be solid with a maximum slope of inch (2.54 cm).
Installation in recess or closet:
Ia dryer installation in a bedroom, bathroom, recess or closet, must be exhausted outdoors.
Your dryer needs the space around it for proper ventilation.
A minimum of 120 square inches(774.2 square cm) of opening, equally divided at the top and bottom of the door, is
required. Air openings are required to be unobstructed when a door is installed. The full length of the door is acceptable.
C
R
Rough-in dimensions
DIMENSIONS
REAR VIEW
50 3/5''
(128.5 cm)
DOOR OPEN 90
28
1/4''
(71.8 cm)