Eaton C-HRG Instruction Leaflet

Eaton C-HRG Instruction Leaflet

Technical information and adjustment procedure

Advertisement

Quick Links

Instruction Leaflet IL019226EN
C-HRG technical information
and adjustment procedure
HAZARDOUS VOLTAGE. WILL CAUSE SEVERE
INJURY OR DEATH. DO NOT OPEN SHUTTER IF THE
EQUIPMENT IS ENERGIZED.
(1) ONLY QUALIFIED ELECTRICAL PERSONNEL
SHOULD BE PERMITTED TO WORK ON THE
EQUIPMENT.
(2) DO NOT ATTEMPT TO INSTALL OR PERFORM
MAINTENANCE ON THE EQUIPMENT WHILE
ENERGIZED. ALWAYS VERIFY THAT NO VOLTAGE
IS PRESENT BEFORE PROCEEDING.
(3) ALWAYS DE-ENERGIZE PRIMARY AND
SECONDARY CIRCUITS BEFORE REMOVING
CIRCUIT BREAKER.
FAILURE TO FOLLOW THESE STEPS FOR ALL
PROCEDURES DESCRIBED IN THIS INSTRUCTION
LEAFLET COULD RESULT IN DEATH, BODILY INJURY,
OR PROPERTY DAMAGE.
SPECIFIC OPERATING PROCEDURES MUST BE
DEVELOPED BY THE RESPONSIBLE PARTY, BECAUSE
OF THE UNIQUE APPLICATION AND VAST VARIETY
OF SYSTEM AND USER REQUIREMENTS. FAILURE
TO DEVELOP SPECIFIC PROCEDURES COULD LEAD
TO IMPROPER USE OR OTHER MORE SERIOUS
CONSEQUENCES.
Effective October 2018
DANGER
WARNING
CAUTION
C-HRG equipment, components,
and setup instructions
The following instructions cannot cover all possible
installations and all details will not be applicable
to all units. When a type C-HRG system is
part of a switchboard or switchgear lineup, the
instructions furnished with the overall assembly
take precedence.
C-HRG wall-mounted unit
C-HRG freestanding
(Separately mounted
NEMA
1 unit
resistors not shown)
®

Advertisement

Table of Contents
loading

Summary of Contents for Eaton C-HRG

  • Page 1 INJURY OR DEATH. DO NOT OPEN SHUTTER IF THE installations and all details will not be applicable EQUIPMENT IS ENERGIZED. to all units. When a type C-HRG system is part of a switchboard or switchgear lineup, the instructions furnished with the overall assembly WARNING take precedence.
  • Page 2: Receiving, Handling, And Storage

    Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Receiving, handling, and storage Refer to assembly drawings provided with the unit for bolt-down hole locations. Bolt directly to wall or floor or channel-iron floor sills. Use 1/2-inch or 3/8-inch bolts for freestanding units and CAUTION 3/8-inch bolts for wall-mounted units.
  • Page 3 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Components SAFETY PRECAUTIONS: ONLY PERSONS TRAINED AND EXPERIENCED IN THE SERVICING OF ELECTRICAL DISTRIBUTION EQUIPMENT SHOULD ATTEMPT TO SERVICE THIS EQUIPMENT. DANGER IF YOU ARE NOT QUALIFIED AND AUTHORIZED TO SERVICE THIS EQUIPMENT, DO NOT DO SO.
  • Page 4: Operation

    Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Operation Test circuit A test circuit is provided to allow the user to quickly determine that the system is working properly. The test circuit will operate only under normal conditions and will not allow testing if the system is sensing a fault.
  • Page 5: Maintenance

    Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Maintenance Ground fault Ground fault detection SAFETY PRECAUTIONS: ONLY PERSONS TRAINED AND EXPERIENCED IN THE Any time a system is energized, a very small ground current will be SERVICING OF ELECTRICAL DISTRIBUTION EQUIPMENT observed.
  • Page 6: Adjustment Procedure

    Check that all wiring is routed away from resistors and that no schematic for tap values and corresponding terminal numbers. wiring passes over resistors The C-HRG typically comes with five resistor settings: Check wiring: check that all wiring connections to resistors and •...
  • Page 7 Both of the methods described below are either tedious or impractical for industrial applications. C-HRG effective. That, in turn, relates to the maximum grounding resistance that can be chosen. To calculate the capacitive charging current of a system:...
  • Page 8 MAY CAUSE DEATH, BODILY INJURY, OR EQUIPMENT DAMAGE. 10. Re-energize the equipment. TURN OFF POWER AT THE SOURCE BEFORE WORKING INSIDE. 11. Put the C-HRG in “test” mode and hold the switch in “test” position. Only qualified personnel should attempt to service 12.
  • Page 9 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Figure 4. Four-wire system—fault detection via current relay Figure 5. Four-wire system—fault detection via voltmeter relay EATON www.eaton.com...
  • Page 10 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Figure 6. Three-wire system—zig-zag grounding transformers, Figure 8. Three-wire system—wye-broken delta grounding fault detection via current relay transformers, fault detection via current relay Figure 7. Three-wire system—zig-zag grounding transformers, Figure 9.
  • Page 11 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Figure 10. Typical enclosure dimensions for NEMA 1 free-standing system—dimensions in inches (mm) EATON www.eaton.com...
  • Page 12 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Figure 11. Typical enclosure dimensions for NEMA 1 wall-mounted system—dimensions in inches (mm) EATON www.eaton.com...
  • Page 13 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Figure 12. Test log EATON www.eaton.com...
  • Page 14 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Figure 13. Standard front control panel detail (voltmeter relay and alarm horn options shown) EATON www.eaton.com...
  • Page 15 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Figure 14. Typical control scheme with fault detection via current relay and alarm option with re-alarm timer Figure 15. Typical control scheme with fault detection via voltmeter, optional loss-of-control power relay, and optional push-to-test lights EATON www.eaton.com...
  • Page 16 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Note: When using clamp-on ammeter to trace fault, always include all three phases within ammeter jaws. Figure 16. Clamp-on ammeter Note: 3W load, one cable per phase, phase C is faulted to ground inside conduit. Ground current can divide into several components, depending on number, conductivity, and location of conduit ground points.
  • Page 17 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 Note: 3W load, one cable per phase, phase C is faulted to ground inside conduit. Ground current can divide into several components, depending on number, conductivity, and location of conduit ground points.
  • Page 18 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 C-HRG maintenance form Date Maintenance item EATON www.eaton.com...
  • Page 19 Instruction Leaflet IL019226EN C-HRG technical information and adjustment procedure Effective October 2018 EATON www.eaton.com...
  • Page 20 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com © 2018 Eaton All Rights Reserved Eaton is a registered trademark. Printed in USA All other trademarks are property Publication No. IL019226EN / Z21760 October 2018 of their respective owners.