Dear Customer, On behalf of everyone at Eaton, we thank you for partnering with us, for trusting us to maintain your business continuity and for preventing downtime at your facility. Our suite of backup power, power distribution and power management products are designed to protect you from a host...
Page 5
3.2 Moving the Current-Limiting Reactor ......................7 3.3 Clearances ..............................8 3.4 Anchoring the Current-Limiting Reactor to the Floor ................... 8 3.5 Installing the Optional Side Car ........................9 4 4 P P o o w w e e r r C C a a b b l l i i n n g g ......................................................... . 1 1 1 1 4.1 Cable Entry .............................
Reactor Power Panels (RPPs) make maintenance of downstream equipment safer by limiting fault current and reducing the risk of arc flash. The 2500A Current-Limiting Reactor is designed to be used as part of a reserve power source for multiple downstream RPPs with Bypass Cabinets. An Current-Limiting Reactor, when used...
A question about any of the information in this manual Eaton Current-Limiting Reactor (2500A) Installation Manual P-164001115—Rev 02 Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates. Phillips and Pozidriv are registered trademarks of Phillips Screw Company.
Page 11
W W a a r r r r a a n n t t y y a a n n d d E E n n d d U U s s e e r r L L i i c c e e n n s s e e A A g g r r e e e e m m e e n n t t To view the warranty please click on the link or copy the address to download from the Eaton website: Eaton Product Warranty https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/backup-...
Page 13
Disconnect power before drilling holes, attaching conduit, or connecting power cables or control wiring. • Use Lock Out/Tag Out procedures. • Wear suitable personal protective clothing and use protective equipment for performing mechanical and electrical installations. • Leave ample space for attaching and routing wires. Eaton Current-Limiting Reactor (2500A) Installation Manual P-164001115—Rev 02...
Page 15
M M o o v v i i n n g g t t h h e e C C u u r r r r e e n n t t - - L L i i m m i i t t i i n n g g R R e e a a c c t t o o r r Move the Current-Limiting Reactor off its pallet with a forklift as follows: The Current-Limiting Reactor or its Side Car is bolted to a pallet. With the pallet resting on the floor, remove the bolts.
A A n n c c h h o o r r i i n n g g t t h h e e C C u u r r r r e e n n t t - - L L i i m m i i t t i i n n g g R R e e a a c c t t o o r r t t o o t t h h e e F F l l o o o o r r The base frame of the Current-Limiting Reactor has (4) holes for anchoring the unit to the floor. Customer provides the ½”...
Page 17
To accommodate the spacing of existing conduit, an optional Side Car provides more cable entry space. The Side Car has removable side panels allowing it to be attached to either side of an Current-Limiting Reactor. On the sides to be joined together: On the Current-Limiting Reactor, remove the top and bottom side panels.
Page 18
Installation Move the Side Car up against the Current-Limiting Reactor so that edges and holes align. Bolt units together at (4) bolt locations (2 upper, 2 lower) in the upper and lower frames. Secure the Side Car to the floor using customer-provided ½" [13 mm] hardware as for the Current-Limiting Reactor.
4 4 . . 1 1 . . 1 1 C C a a b b l l e e E E n n t t r r y y P P a a n n e e l l s s The Current-Limiting Reactor has (2) top and (2) bottom cable entry panels. Installers can create up to (5) 4.0"...
Page 20
P P o o w w e e r r C C o o n n n n e e c c t t i i o o n n s s IMPORTANT • A licensed electrician must install the Current-Limiting Reactor and connect external wiring. • Installers should use Lock-Out/Tag-Out procedures and observe other precautions listed in the introductory Safety section.
Page 21
W W i i r r i i n n g g t t h h e e P P T T 1 1 0 0 0 0 S S e e n n s s o o r r The Current-Limiting Reactor has a PT100 sensor installed in the reactor coil. The front upper panel of the Current-Limiting Reactor cabinet has a compartment with terminal blocks that are wired to the sensor.
Page 22
Installers wire from overhead to the top of the termnal blocks. The factory wires from the sensor to the bottom of the Cover plate has (2) termnal blocks. 1/4 turn screws. Eaton Current-Limiting Reactor (2500A) Installation Manual P-164001115—Rev 02...
Page 25
C C h h a a p p t t e e r r 5 5 S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Eaton Service contracts help to provide the added insurance that the reliability of your critical power systems is intact.
Page 26
Service and Maintenance Eaton Current-Limiting Reactor (2500A) Installation Manual P-164001115—Rev 02...
Page 29
C C h h a a p p t t e e r r 7 7 C C u u r r r r e e n n t t - - L L i i m m i i t t i i n n g g R R e e a a c c t t o o r r 2 2 5 5 0 0 0 0 A A D D r r a a w w i i n n g g s s Eaton Current-Limiting Reactor (2500A) Installation Manual P-164001115—Rev 02...