Riken Keiki SF6 Series Operator's Manual
Riken Keiki SF6 Series Operator's Manual

Riken Keiki SF6 Series Operator's Manual

Gas purity monitor
Hide thumbs Also See for SF6 Series:

Advertisement

Quick Links

SF6 GAS PURITY MONITOR
Request for the Customers
Read and understand this manual before using the gas monitor.
Use the gas monitor in accordance with the manual.
Regardless of warranty period, we shall not make any compensation for accidents and
damage caused by using this product.
Because this is a safety unit, daily maintenance, gas calibration for every six months, and
regular maintenance must be performed.
The sensors of the gas monitor, having its sensor life, must be replaced at regular intervals.
If any abnormality was found in the gas monitor, notify them to Riken Keiki headquarters or
authorized local representative immediately.
FI-21-SF6
Operator's Manual
PT3E-0220

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SF6 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Riken Keiki SF6 Series

  • Page 1 • The sensors of the gas monitor, having its sensor life, must be replaced at regular intervals. • If any abnormality was found in the gas monitor, notify them to Riken Keiki headquarters or authorized local representative immediately.
  • Page 2 PT3E-0220 Introduction Thank you for purchasing the Model FI-21-SF6. This instrument is a portable gas monitor to measure SF6 Purity levels. This instruction manual is a guidebook on how to operate the Model FI-21-SF6. Both beginner users and experienced users must read this manual and understand the contents thoroughly prior to operation.
  • Page 3: Table Of Contents

    PT3E-0220 Index 1. CAUTION ON USAGE…………………………………………………………………...3 2. PARTS AND PART FUNCTIONS……………………………………………………..4 3. STANDARD ACCESSORIES……...……………………………………..……………..7 4. TUBING STRUCTURE..…….…………………..…………………………………….…8 5. MEASURING PROCEDURES.….…..……….…….…………...……………………..9 5-1. Preparations for measuring….…..………………..…………..…………………..9 5-2. Power On…………………………………………….……………..…………………...9 5-3. AIR CAL (Zero Calibration)………………………………….…………...…………..10 5-4. Apply the sample gas…………….…….……...……………………….….…………10 5-5. Start measuring……….……………………..………………………..………………10 5-6.
  • Page 4: Caution On Usage

    PT3E-0220 1. CAUTION ON USAGE The following caution items must be followed to maintain the performance and safety of the instrument. Danger Specification of this instrument is based on a non-explosive structure. Do not use it in a place specified as a hazardous area. Make any solutions for exhaust gas emitted from GAS OUT to avoid harmful gas from emission (e.g.
  • Page 5: Parts And Part Functions

    PT3E-0220 2. PARTS AND PART FUNCTIONS Flow Meter A Flow Meter B Pressure Regulator GAS IN GAS OUT / AIR IN Measuring Unit “SAMPLE GAS – AIR” Switch Cock Inlet for the sample gas. A specific pressure-proof tube must be connected to the inlet, and the GAS IN sample gas must be supplied through the tube.
  • Page 6 PT3E-0220 Measuring Unit Press this key to turn the power on until the buzzer beeps. Keep POWER key pressing the key for approximately 3 seconds to turn the power off. Concentration is displayed. The time, battery remainder, and LCD display measure of gas and base gas are displayed as well.
  • Page 7 PT3E-0220 Right side Left side (11) (12) (10) (13) (14) (15) Bottom (16) GAS IN Inlet for measuring gas. (10) Outlet connected to the reference gas chamber and the pressure (11) REF. OUT sensor. The outlet must be exposure to the fresh air at atmospheric pressure.
  • Page 8: Standard Accessories

    PT3E-0220 3. STANDARD ACCESSORIES The following parts are standard and optional accessories for the FI-21-SF6. Nipple for the gas sampling point Fix the screw-cutting side to the gas sampling point, and connect a pressure-proof tube end to the coupler joint side. Pressure-proof tube Connect a pressure-proof tube end to the nipple for the gas sampling point, and connect the opposite tube end to GAS IN on the sampling box.
  • Page 9: Tubing Structure

    PT3E-0220 4. TUBING STRUCTURE A figure shows tubing structure of FI-21-SF6. A sequence of actions for each case that “SAMPLE GAS – AIR” Switch Cock is turned lengthways and sideways is indicated below. While “SAMPLE GAS – AIR” Switch Cock is turned to sideways, Air (Zero Gas) is supplied from the GAS OUT / AIR IN as long as a pump inside the Measuring Unit works.
  • Page 10: Measuring Procedures

    PT3E-0220 5. MEASURING PROCEDURES 5-1. Preparations for measuring Apply the power to the instrument. AC adaptor Plug the specific AC adaptor in the 6VDC Interface located left side on the sampling box. Picture: Left side on the sampling box Alkaline batteries Screw Take out the Measuring Unit from the sampling box, and set 4 pcs batteries (Size C) in the battery box located bottom of the...
  • Page 11: Air Cal (Zero Calibration)

    PT3E-0220 5-4. Apply the sample gas Connect the pressure-proof tube to the GAS IN on the sampling box and apply the sample gas from the sampling point. The sample gas pressure should then be less than 0.7 MPa. Make sure that the pressure regulator on the panel is set 0.1±0.02MPa.
  • Page 12: Displays And How To Operate

    PT3E-0220 6. DISPLAYS AND HOW TO OPERATE 6-1. Initial Displays The initial displays are automatically showed up after the power is turned on. The self-diagnostic display is appeared firstly. If there is no serious error found in the Measuring Unit, the setting confirmation display is then showed up for two seconds and it proceeds to the basic display for measuring mode.
  • Page 13: Basic Display For Measuring Mode

    PT3E-0220 6-2. Basic display for Measuring Mode When data is saved, this Battery life symbol appears. Clock (0-24 hour) 24:00 concentration displayed during the measurement. If the SF6 99.8 concentration exceeds 99.9%, the display is to be 99.9%up. SF6 The data No. appears when the in...
  • Page 14: Setting Display (Setting Mode)

    PT3E-0220 6-3. Setting Display (Setting Mode) The Setting Mode is for “adjusting the time”, ”adjusting the LCD contrast ” and “reviewing the saved data”. Enter the Setting Mode by pressing MODE key more than 2 seconds after the Power Once the Setting Mode is on, the display shown right appears. 12:00 Move the cursor (black bar) with the ▼▲...
  • Page 15: Lcd Contrast

    PT3E-0220 Delete the saved data (CLEAR SAVED DATA) This is an item to delete the saved data. Select the “CLEAR SAVED 12:00 DATA” with the▼▲ keys at the display shown right, and press the C A N C E L C...
  • Page 16: Maintenance

    PT3E-0220 7. MAINTENANCE 7-1. Daily check 1). Check there are any damages on the switches, lamps, display, or body. 2). Check the battery voltage. 3). Check there are no error messages after the Power On. 4). Check the Pressure Regulator is adjustable to be 0.1±0.02MPa while “SAMPLE GAS - AIR” Switch Cock is turned lengthways.
  • Page 17: Disposal Of The Instrument

    PT3E-0220 8. DISPOSAL OF THE INSTRUMENT There is no harmful material contained in the instrument and its component parts. When the instrument is desired to be disposed, take an appropriate disposal method based on local regulation. 9. TROUBLE SHOOTING The following trouble shootings do not cover all problems, however those that occur most frequently are mentioned to help you to find the causes and the solutions.
  • Page 18: Specifications

    PT3E-0220 10. SPECIFICATIONS Measuring Unit SF6 PURITY MONITOR Model FI-21-SF6 Measuring Principle Optical Interferometric Method Measuring Gas SF6 (Base Gas = AIR) Measuring Range 0 ~ 100 VOL% (Minimum Digit: 0.1 VOL%) Accuracy ±1 VOL% Display LCD, Digital Display Flow rate Over 0.4 L/min Sampling Pressure 0.15 ~ 0.7 MPa gauge...
  • Page 19: Measuring Principle

    PT3E-0220 11. MEASURING PRINCIPLE The refractive index of a mixture gas is determined by the kinds of composing gases and the mixture ratio. As long as the kinds of composing gases are known, the mixture ratio (concentration) is determined by measuring the refractive index. The optical interferometer applied for the FI-21-SF6 displays “Interference Stripes”, which moves proportional to the refractive index, on the CCD.
  • Page 20: Warranty

    PT3E-0220 12. WARRANTY RIKEN KEIKI CO., LTD., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RIKEN KEIKI CO., LTD., Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.