Monitor and Control of Digital I/O

1. General Description

The iPIO is a network attached, web enabled digital input and output device. The iPIO can be controlled
and monitored with a standard web browser. Multiple iPIO devices can communicate amongst
themselves to transport I/O information across the network. Each iPIO has controllable form C relays,
and digital inputs.
Each channel of the iPIO is independently configurable, allowing selection of what IP addresses to
deliver to and on what channel. Highly flexible telemetry systems can be developed with these simple
devices.
iPIO-2816_v180808n

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the iPIO-8 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Dataprobe iPIO-8

  • Page 1: General Description

    Monitor and Control of Digital I/O 1. General Description The iPIO is a network attached, web enabled digital input and output device. The iPIO can be controlled and monitored with a standard web browser. Multiple iPIO devices can communicate amongst themselves to transport I/O information across the network.
  • Page 2: Table Of Contents

    10. Firmware Upgrades ........25 5.2. Telnet ........... 11 5.3. SNMP ........... 11 11. Specifications ..........26 5.4. Email Notifications ........ 12 12. Technical Support and Warranty ..... 28 5.5. Dataprobe Exchange Protocol (DxP) ..13 iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 2...
  • Page 3: Model Identification And Features

    A/C Power Supply Height 2.02” Width 5.00” Depth 7.32” 3.4. Optional Accessories Mounting Kit # 1920034. See Section 4.8 High Current Relay Module # 1340076. See Section 4.4 Replacement Power Supply # 1930085 iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 3...
  • Page 4: Hardware Installation

    Disconnect power and all cables prior to input configuration. When connecting +VDC, connect the positive voltage to the terminal marked + and the negative or ground to the terminal marked G. Status DC Voltage Open >3VDC Closed <=0VDC iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 4...
  • Page 5: Relays

    16. There are eight jumpers representing inputs 1-8 on the iPIO-8 and iPIO-16. Jumpers 9-16 on the iPIO- 16 are located on the daughter board for the inputs. An arrow indicates jumper 1 and 9. See photo:...
  • Page 6: Switching Higher Current

    4.5. Power The iPIO-2, iPIO-8 and iPIO-16 are provided with a power supply, item 1930085. The supply is rated for 100- 240VAC 50/60 Hz. and is supplied with a line cord for North America. For locations outside of North America, use an appropriate power adaptor or replace the cord with a suitable cord for your location.
  • Page 7: Network

    During power up sequence, LEDs will be off until boot complete, then flash once, and then set to their current status. Link Network Connected Network Activity. During power up sequence, Act LED will be solid on until boot process is complete. After boot, LED blinking indicates network activity iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 7...
  • Page 8: Wall And Din Mounting

    Part # 1920034 Wall and DIN Mounting Kit Remove all cables from the unit prior to installing or removing any mounting hardware. Wall Mounting iPIO-8 and iPIO-16 Install the wall mounting ears to the unit using the four silver screws.
  • Page 9 Use the ear tabs on the Unit to directly mount to wall or backboard Mount to wall or backboard with proper hardware. DIN Rail Mounting iPIO-8 and iPIO-16 Install the Intermediate bracket onto the bottom of the unit using the 4 silver screws.
  • Page 10 Mount to DIN Rail DIN Rail Mounting iPIO-2 Install the DIN rail clips using the four black screws. Clips can be mounted for either vertical or horizontal aspect. Mount to DIN Rail iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 10...
  • Page 11: Communications Options

    Telnet Factory Default Port Section 9 for Telnet and CLI details 5.3. SNMP The iPIO is SNMP manageable. Up to four SNMP managers can be defined for the purpose of delivering status Inform messages. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 11...
  • Page 12: Email Notifications

    <state name> Example: From: <mydataprobe@comcast.net> Date: Thu, Oct 3, 2013 at 5:14 PM Subject: Input Change To: testlab@dataprobe.com Shop Floor - Houston Input 16 Back Door is Open Other emails use similar syntax. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 12...
  • Page 13: Dataprobe Exchange Protocol (Dxp)

    The protocol for communication between iPIO units can be used by software developers to create custom applications for a wide variety of applications. Dataprobe makes the protocol freely available on its website, as well as sample code in a variety of formats.
  • Page 14: Web Browser Operation

    The top menu bar is only visible and accessible to users with administrative rights. It allows access to the Setup and Administration pages of the unit. Read the following sections for details on setup and administration. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 14...
  • Page 15: Web Browser Setup

    Click save Contact Dataprobe Technical Support for to save the changes. You will details. then be prompted to reboot the iPIO. Click on the Reboot Required button. The iPIO will iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 15...
  • Page 16 The Network Setup page also allows for changing of the port assignment for HTTP, HTTPS and inter-iPIO protocols. Dataprobe recommends changing the Web port for units that will be connected to the Internet. This will minimize the number of hacker attacks that the iPIO will be subject to. If a port other than the default Port 80 is used for web browser access, the port must specifically be used in the URL when accessing the iPIO.
  • Page 17: Email Setup

    Each manager defined here will receive traps. Read & Write Community. Set the SNMP Read Community and Write Community strings here. Send Trap on Change Set which events will generate SNMP Traps. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 17...
  • Page 18: Input Setup

    Click Save when done, before moving to the next input or setup section LED Status The user may select upon what state of the input the LED for that channel will be ON or Off. Select with the radio button. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 18...
  • Page 19: Relay Setup

    To add the first device, click on Add Device. This will generate the setup screen for the first remote. To add additional remotes, click on Add Device for each one. Up to 32 remote units can be programmed. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 19...
  • Page 20 If the Auto Update feature is enabled on the Device Setup page, the iPIO will periodically transmit its status to the remote unit. If the On Reconnect feature is enabled, the iPIO will transmit its status whenever the connection to the remote is established or re-established. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 20...
  • Page 21: Remote Setup Applications

    The flexibility of the iPIO allows many other combinations of control and reporting. Contact Dataprobe Technical Support for assistance in getting the most out of your iPIO.
  • Page 22: Web Browser Administration

    Click on Choose File to select a .conf file to upload. Select the file and click Open. The file name will be listed next to the Choose File button. Use the Keep Network IP Settings to restore all settings EXCEPT the iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 22...
  • Page 23: Factory Defaults

    8.4. Reboot A Reboot button provides a restart of the iPIO system. Once the Reboot button is pushed the device will reboot. Once the reboot is completed, the device will automatically reconnect. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 23...
  • Page 24: Telnet And Cli

    192.168.1.254 <xxx.xxx.xxx.xxx> set subnet Sets the subnet mask in dotted decimal 255.255.255.0 <xxx.xxx.xxx.xxx> set gateway Sets the gateway in dotted decimal 0.0.0.0 <xxx.xxx.xxx.xxx> set telnet port <xxxxxx> Sets the telnet port (0-65535) iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 24...
  • Page 25: Firmware Upgrades

    Click OK when all the details are entered. 3) The upload will begin, progress bar will be displayed. 4) When firmware upload completed, WAIT 2 Minutes. iPIO will automatically reset and be ready for use. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 25...
  • Page 26: Specifications

    1A Max 1mA Min Resistance 100 milliohms (initial value) Operations 5 Million, mechanical. 100K at maximum load iPIO-2 2 Form C Relays iPIO-8 8 Form C Relays iPIO-16 16 Form C Relays iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 26...
  • Page 27 DHCP Assigned or Static IP Address Email to SMTP Server SNMP V2 Manageable. MIB Supplied Inter Device Communications via DxP Protocol supplied. 128 bit AES Encryption optional Selectable Port assignments for Web and DxP Protocol. iPIO-2816_v180808n iPIO-2, iPIO-8, iPIO-16 Users Guide Page 27...
  • Page 28: Technical Support And Warranty

    90 days, whichever is greater. If Purchased from Dataprobe Inc.; Service under this Warranty is obtained by shipping the product (with all charges prepaid) to the address below. Seller will pay return shipping charges within the United States. Call Dataprobe Technical Service to receive a Return Materials Authorization (RMA) Number prior to sending any equipment back for repair.