No. Error Code
29
E396
DC voltage sensor error of Fan2
30
E399
Heat sink temperature sensor error of Fan2
31
E403
Compressor down due to freeze protection control
32
E404
System stop due to overload protection control
33
E416
System stop due to discharge temperature
34
E422
Blockage detected on high pressure pipe
35
E425
Reverse phase or open phase
36
E440
Heating mode restriction due to high air temperature
37
E441
Cooling mode restriction due to low air temperature
38
E446
Error due to operation failure of Fan1
39
E447
Motor wire of Fan1 is not connected
40
E448
Lock error on Fan1 of outdoor unit
41
E452
Error due to ZCP detection circuit problem or power failure
42
E453
Error due to overheated motor of outdoor unit's Fan1
43
E455
Error due to overheated IPM of Fan1
44
E458
Fan speed error
45
E461
Error due to operation failure of inverter compressor
46
E462
System stop due to full current control
47
E463
Over current trip / PFC over current error
48
E464
IPM Over Current(O.C)
49
E465
Comp. Over load error
50
E466
DC-Link voltage under/over error
Error due to abnormal rotation of the compressor or unconnected
51
E467
wire of compressor
52
E468
Error on current sensor (Short or Open)
53
E469
Error on DC-Link voltage sensor (Short or Open)
Outdoor EEPROM checksum error between MAIN and INVERTER
54
E471
(ACKXAPNH)
55
E472
AC Line Zero Cross Signal out
56
E473
Comp Lock error
57
E474
Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
58
E475
Error on inverter fan 2
59
E478
Error due to overcurrent of Fan1
60
E484
PFC Overload (Over current) Error
61
E485
Error on input current sensor of inverter 1 (Short or Open)
62
E486
Over-voltage/low-voltage error of Fan1
Samsung Electronics
Meaning
Remarks
FAN2 error
FAN2 error
Check Outdoor Cond.
Check Comp. when it start
-
1. Check if the service valve is open
2. Check for refrigerant leakage(pipe connections,
heat exchanger) and charge refrigerant if
necessary
3. Check if there's any blockage on refrigerant
cycle(indoor unit/outdoor unit)
4. Check if additional refrigerant has been added
after pipe extension
Check whether 3 phase is reversed or opened.
HEATING
COOLING
FAN1 error
FAN1 error
FAN1 error
-
FAN1 error
FAN1 error
FAN1 ERROR
-
-
Check OLP sensor
IPM
-
Check AC Power and DC Link Voltage
Check Comp wire
Check Outdoor Inverter PBA.
-
Check Outdoor EEPROM PBA
-
-
heck Outdoor Inverter PBA
FAN2 ERROR
FAN1 error
Check Outdoor Inverter PBA.
Check Outdoor EEPROM PBA
FAN1 error
4-5