Outdoor Trouble Shooting - Samsung AC052MNMSEH Service Manual

System air conditioner, indoor/outdoor unit
Hide thumbs Also See for AC052MNMSEH:
Table of Contents

Advertisement

4-2 Outdoor Trouble shooting

The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for
Authorized Service Center.
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER
PCB.
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
No. Error Code
Error due to repeated address setting(when 2 or more devices has
1
E108
same address within the network)
2
E121
Error on indoor temperature sensor of indoor unit(Short or Open) Indoor unit Room Thermistor Open/Short
3
E122
Error on EVA IN sensor of indoor unit(Short or Open)
4
E123
Error on EVA OUT sensor of indoor unit(Short or Open)
5
E153
Error on float switch (2nd detection)
6
E154
RPM feedback error of indoor unit
7
E162
Outdoor unit EEPROM Read/Write error (H/W)
8
E163
Outdoor unit EEPROM Read/Write error (Option)
9
E198
Error on thermal fuse of indoor unit (Open)
"Communication error between indoor and outdoor
10
E201
unit(Installation number setting error repeated
indoor unit address,indoor unit communication cable error)"
"Communication error between indoor and outdoor
11
E202
unit(Communication error on all indoor unit,
outdoor unit communication cable error)"
Communication error on all PBA within the outdoor unit
12
E205
C-Box,communication cable error
E206-C002 : Fan PBA communication error, E206-C003 : INV PBA
13
E206
communication error
14
E221
Error on outdoor temperature sensor (Short or Open)
15
E231
Error on outdoor COND OUT sensor (Short or Open)
Error on discharge temperature sensor of compressor 1 (Short or
16
E251
Open)
17
E320
Error on OLP sensor (Short or Open)
18
E346
Error due to operation failure of Fan2
19
E347
Motor wire of Fan2 is not connected
20
E348
Lock error on Fan2 of outdoor unit
21
E353
Error due to overheated motor of outdoor unit's Fan2
22
E355
Error due to overheated IPM of Fan2
23
E378
Error due to overcurrent of Fan2
24
E386
Over-voltage/low-voltage error of Fan2
25
E387
Hall IC connection error of Fan2
26
E389
V-limit error on Fan2 of compressor
27
E391
Error due to DataFlash of Fan2
28
E393
Output current sensor error of Fan2
4-4
Meaning
Remarks
Check on repeated indoor unit main address
Indoor unit EVA_IN Thermistor Open/Short
Indoor unit EVA_OUT Thermistor Open/Short
"Indoor unit Float Switch Open/Short Drain Pump
operation Check"
Check on indoor unit indoor Fan operation
Check Outdoor EEPROM PBA
Check Outdoor EEPROM Data
Thermal Fuse Open Check of indoor unit Terminal
Block
Check indoor quantity setting in outdoor
Check electrical connection and setting between
indoor unit and outdoor unit
-
-
Check Outdoor sensor Open / Short
Check Cond-Out sensor Open / Short
Check Discharge sensor Open / Short
Check OLP sensor Open / Short
FAN2 error
FAN2 error
FAN2 error
FAN2 error
FAN2 error
FAN2 error
FAN2 error
FAN2 error
FAN2 error
FAN2 error
FAN2 error
Samsung Electronics