Technical Data - Samson TROVIS 6600 Mounting And Operating Instructions

Automation system. web terminal
Hide thumbs Also See for TROVIS 6600:
Table of Contents

Advertisement

Technical data

4 Technical data
Power supply
Power supply
Power consumption
PE
Temperature range
Operation
Transportation and storage
Relative humidity
Electromagnetic compatibility
Noise emission
Noise immunity
Device safety
Class of protection
Overvoltage category
Degree of contamination
Degree of protection
CE
Performance
CPU
RAM
Display
Resolution
Interfaces
USB
Ethernet 10/100 with 802.3af
PoE (Power over Ethernet)
Compliance
6
24 V DC or Power over Ethernet (PoE)
7.4 W
a) Wire cross-section stranded with ferrule without plastic sleeve,
max. 1.5 mm²
b) Wire cross-section stranded with ferrule with plastic sleeve,
max. 0.5 mm²
0 to 50 °C
0 to 70 °C
10 to 90 %, non-condensing
According to EN 61000-6-3
According to EN 61000-6-2
II according to EN 61140: 2003
II according to EN 60664-1
2 according to EN 60664-1
IP 65 at the front, IP 20 at the back
EN 55022: 2010 Class B
EN 55024: 2010
EN 61000-6-2: 2005
Cortex A8 processor with ultra low voltage, 1 GHz
512 MB LPDDR RAM
7" widescreen LED-TFT monitor, projected capacitive touch screen
800 x 480 pixels, can be used for microbrowser with 758 x 480
pixels
Two USB 2.0 A ports, one mini USB port
1 x RJ45
·
EB 6616 EN