Technical Data - Samson TROVIS 6616 Mounting And Operating Instructions

Web terminal for trovis 6600 automation system
Hide thumbs Also See for TROVIS 6616:
Table of Contents

Advertisement

Markings on the device

3.2 Technical data

Power supply
Supply voltage
Power consumption
PE
Temperature range
Operation
Transportation and storage
Relative humidity
Electromagnetic compatibility
Noise emission
Noise immunity
Device safety
Class of protection
Overvoltage category
Degree of contamination
Degree of protection
CE
Performance
CPU
RAM
Display
Resolution
Interfaces
USB
Ethernet 10/100 with 802.3af PoE
(Power over Ethernet)
Compliance
10
24 V DC or Power over Ethernet (PoE)
7.4 W
a) Wire cross-section stranded with ferrule without plastic
sleeve, max. 1.5 mm²
b) Wire cross-section stranded with ferrule and plastic sleeve,
max. 0.5 mm²
0 to 50 °C
0 to 70 °C
10 to 90 %, non-condensing
According to EN 61000-6-3
According to EN 61000-6-2
II according to EN 61140: 2003
II according to EN 60664-1
2 according to EN 60664-1
IP 65 at the front, IP 20 at the back
EN 55022: 2010 Class B
EN 55024: 2010
EN 61000-6-2: 2005
i.MX6
1 GB RAM
7" widescreen LED-TFT monitor, projected capacitive touch
screen
800x480 pixels, can be used for applications with 758x480
pixels
1x USB 2.0 A
1x RJ-45
·
EB 6616 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

6616-0000

Table of Contents