Selectable output strobes, horns, and horn/strobes

Advertisement

CANDELA SELECTION
Adjust the slide switch on the rear of the product to the desired candela set-
ting in the small window on the front of the unit. All products meet the light
output profiles specified in the appropriate UL Standards. See Figures 1-3.
Use Table 1 to determine the current draw for each candela setting. For K
series products used outdoors at low temperatures, listed candela ratings must
be reduced in accordance with Table 2.
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work
on either 12V or 24V power supplies. The products are not listed for 12V op-
erating voltages when set to any other candela settings. For 4-Wire products,
total current draw may be determined by adding current draw for the specific
candela selection and the current draw for the specific horn selection use
Table 1 and Table 3.
FIGURE 1. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS
TO FLOOR
Percent of
Degrees*
Rating
0
100
5-25
90
30-45
75
50
55
60
45
65
35
70
35
75
30
80
30
85
25
90
25
Figures 1-3 list the minimum light output requirements per UL1971.
FIGURE 2. LIGHT OUTPUT -
HORIZONTAL DISPERSION
FIGURE 3. LIGHT OUTPUT - VERTICAL DISPERSION, WALL TO FLOOR
This is generated text for figtxt.
*Tolerance of ±1 degree is permitted.
TABLE 1. STROBE CURRENT DRAW (mA) FOR S, SC, P4 & PC4 SERIES:
Standard Candela Range
High Candela Range
TABLE 2. CANDELA DERATING:
HORN SELECTION
Turn the rotary switch on the back of the product to the desired setting. For
Percent of
Degrees*
horn and 4-wire horn/strobe products, the current draw for each setting is
Rating
listed in Table 3. For 2-wire horn/strobe products (P2 series), current draws
0
100
are listed in Tables 4 and 5. The sound output measurement for each horn
5-25
90
setting is shown in Table 6.
30-45
75
TABLE 3. HORN CURRENT DRAW (mA) FOR H, P4 & PC4 SERIES:
50
55
55
45
Pos
60
40
65
35
1
70
35
2
75
30
3
80
30
4
85
25
5
90
25
6
Compound 45
24
7
to the right
8
Compound 45
24
9
to the right
NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC.
If the NAC voltage is held constant, the horn output will remain constantly on.
Percent of
Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
Degrees*
Rating
0
100
5-30
90
35
65
40
46
45
34
50
27
55
22
60
18
65
16
70
15
75
13
80
12
85
12
90
12
2
Candela
15
15/75
30
75
95
110
115
135
150
177
185
Listed Candela
(K Series Outdoor Applications Only)
15
15/75
30
75
95
110
115
135
150
177
185
8–17.5 Volts
Sound Pattern
dA Out
DC
Temporal
High
57
Temporal
Medium
44
Temporal
Low
38
Non-temporal
High
57
Non-temporal
Medium
42
Non-temporal
Low
41
Coded
High
57
Coded
Medium
44
Coded
Low
40
8–17.5 Volts
16–33 Volts
DC
FWR
DC
FWR
123
128
66
71
142
148
77
81
NA
NA
94
96
NA
NA
158
153
NA
NA
181
176
NA
NA
202
195
NA
NA
210
205
NA
NA
228
207
NA
NA
246
220
NA
NA
281
251
NA
NA
286
258
Candela rating at –40°F
Do not use below 32°F
44
70
110
115
135
150
177
185
16–33 Volts
FWR
DC
FWR
55
69
75
49
58
69
44
44
48
56
69
75
50
60
69
44
50
50
55
69
75
51
56
69
46
52
50
I56-2769-020R