System Sensor SpectrAlert Advance P2R Installation And Maintenance Instructions

System Sensor SpectrAlert Advance P2R Installation And Maintenance Instructions

Selectable output strobes, horns, and horn/strobes

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
Selectable Output Strobes, Horns, and Horn/Strobes
For use with the following models: P2R, P2RH, P2RK, P2RHK, P2W, P2WH, P4R, P4RH, P4RK, P4RHK, P4W, P4WH, SR, SRH, SRK, SRHK, SW, SWH, PC2R, PC2RH,
PC2RK, PC2RHK, PC2W, PC2WH, PC4R, PC4RH, PC4RK, PC4RHK, PC4W, PC4WH, SCR, SCRH, SCRK, SCRHK, SCW, SCWH, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,
P2R-P, P2W-P, P2RH-P, P2WH-P, SCR-P, SCW-P, SCRH-P, SCWH-P, PC2R-P, PC2W-P, PC2RH-P, PC2WH-P, P4R-P, P4RH-P, P4W-P, P4WH-P, SR-SP, SRH-SP, P2R-SP, P2RH-SP,
SCW-SP, SCWH-SP, PC2W-SP, PC2WH-SP

Specifications

General Specifications
Standard Operating Temperature:
K Series Operating Temperature:
Humidity Range:
Strobe Flash Rate:
Nominal Voltage:
Operating Voltage Range:
Operating Voltage with MDL:
1
P, S, PC, & SC products will operate at 12 V nominal only for 15 & 15/75 cd.
Mechanical Specifications
Input terminal wire gauge:
Ceiling mount dimensions (including lens):
Wall mount dimensions (including lens):
Horn dimensions:
The products in this manual may be covered by one or more of the following patents:
5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,522,261; 6,661,337; 6,822,400; 6,833,783; 6,856,241.
General Description
The SpectrAlert Advance series of notification appliances
offers a comprehensive range of red and white wall, ceiling,
and outdoor products including horns, strobes, and horn/
strobes. These products are electrically backward compat-
ible with the previous generation of notification appliances.
While there are products specifically designed for use on
the ceiling or the wall, the products are listed to be used
in either application, i.e., wall products could be used on
the ceiling. SpectrAlert products are designed to be used
in either 12 or 24 volt DC or full wave rectified (FWR) sys-
tems. If required, the MDL module may be used in order to
provide synchronization.
NOTICE: This manual shall be left with the owner/user of
this equipment.
Fire Alarm System Considerations
The National Fire Alarm Code, NFPA 72, requires that all
horns, used for building evacuation installed after July 1,
1996, produce temporal coded signals. Signals other than
those used for evacuation purposes do not have to produce
the temporal coded signal.
Power Supply Considerations
Panels typically supply DC filtered voltage or FWR (full
wave rectified) voltage. The system design engineer must
calculate the number of units used on a loop based on the
type of panel supply. Be certain the sum of all the device
currents does not exceed the current capability of the panel.
D690-03-00
32°F to 120°F (0°C to 49°C)
–40°F to 151°F (FM approved to –31°F); See note for Table 2.
10 to 93% non-condensing (indoor products)
1 flash per second
Regulated 12DC/FWR or regulated 24DC/FWR
8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal)
9 to 17.5 V (12V nominal) or 17 to 33 V (24 V nominal)
12 to 18 AWG
6.8˝ diameter×2.5˝ high (173 mm diameter×64 mm high)
5.6˝L×4.7˝W×2.5˝D (142 mm L×119 mm W×64 mm D)
5.6˝L×4.7˝W×1.3˝D (142 mm L×119 mm W×33 mm D)
Calculations are based on using the device current found
in the subsequent charts and must be compatible with the
current specified for the panel or power supply used.
Wire Sizes
The designer must be sure that the last device on the circuit
has sufficient voltage to operate the device within its rated
voltage. When calculating the voltage available to the last
device, it is necessary to consider the voltage drop due to
the resistance of the wire. The thicker the wire, the smaller
the voltage drop. Generally, for purposes of determining the
wire size necessary for the system, it is best to consider all
of the devices as "lumped" on the end of the supply circuit
to simulate worst case. For the most accurate voltage drop
calculations use the System Sensor voltage drop calculator
available on the web or CD-ROM.
Approximate wire resistance:
18 AWG solid: 8 ohms/1000 ft.
16 AWG solid: 5 ohms/1000 ft.
14 AWG solid: 3 ohms/1000 ft.
12 AWG solid: 2 ohms/1000 ft.
Note: If Class A wiring is installed, the wire length may be
up to twice as long as on non-fault tolerant circuits.
Note: For 24 volt applications, the total number of strobes
on a single NAC must not exceed 40, with a maximum loop
resistance of 120 ohms. For 12 volt applications, the total
number of strobes must not exceed 12, with a maximum
loop resistance of 30 ohms.
1
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
1
I56-2769-003R

Advertisement

loading

Summary of Contents for System Sensor SpectrAlert Advance P2R

  • Page 1: Specifications

    INSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630/377-6495 Selectable Output Strobes, Horns, and Horn/Strobes www.systemsensor.com For use with the following models: P2R, P2RH, P2RK, P2RHK, P2W, P2WH, P4R, P4RH, P4RK, P4RHK, P4W, P4WH, SR, SRH, SRK, SRHK, SW, SWH, PC2R, PC2RH, PC2RK, PC2RHK, PC2W, PC2WH, PC4R, PC4RH, PC4RK, PC4RHK, PC4W, PC4WH, SCR, SCRH, SCRK, SCRHK, SCW, SCWH, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P, P2R-P, P2W-P, P2RH-P, P2WH-P, SCR-P, SCW-P, SCRH-P, SCWH-P, PC2R-P, PC2W-P, PC2RH-P, PC2WH-P, P4R-P, P4RH-P, P4W-P, P4WH-P, SR-SP, SRH-SP, P2R-SP, P2RH-SP, SCW-SP, SCWH-SP, PC2W-SP, PC2WH-SP Specifications General Specifications Standard Operating Temperature: 32°F to 120°F (0°C to 49°C) K Series Operating Temperature: –40°F to 151°F (FM approved to –31°F); See note for Table 2. Humidity Range: 10 to 93% non-condensing (indoor products) Strobe Flash Rate: 1 flash per second Nominal Voltage: Regulated 12DC/FWR or regulated 24DC/FWR Operating Voltage Range: 8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal) Operating Voltage with MDL: 9 to 17.5 V (12V nominal) or 17 to 33 V (24 V nominal) P, S, PC, & SC products will operate at 12 V nominal only for 15 & 15/75 cd. Mechanical Specifications Input terminal wire gauge: 12 to 18 AWG...
  • Page 2 Candela Selection for P, S, PC, & SC series models Horn Selection for P, PC, & H series models For strobe candela selection, adjust the slide switch located Horn setting selection is accomplished by using the rotary on the rear of the product while watching the viewing win- switch on the back of the product (see Table 5). The current dow under the reflector on the front of the unit. Use Table draw for various horn settings for horn and 4-wire horn/ 1 to determine current draw at various candela settings. strobe products is listed in Table 6. The current draw for Table 2 can be used to derate the candela rating for low various horn and candela settings for 2-wire horn/strobe temperature operation. Tables 3 & 4 can be used to deter- products (P2 series) is shown in Table 7 & 8. The sound...
  • Page 3 Table 7. 2-wire Horn/Strobe Standard Candela Range (15–115 cd) Current Draw (mA) 8–17.5 Volts 16–33 Volts DC Input 15/75 15/75 Temporal High Temporal Medium Temporal Low Non-temporal High Non-temporal Medium Non-temporal Low FWR Input Temporal High Temporal Medium Temporal Low Non-temporal High Non-temporal Medium Non-temporal Low Table 8. 2-wire Horn/Strobe High Candela Range (135–185 cd) Current Draw (mA) 16–33 Volts 16–33 Volts DC Input FWR Input Temporal High Temporal High Temporal Medium Temporal Medium Temporal Low...
  • Page 4 Mounting installed using the proper SpectrAlert Advance water- tight junction box. The wall mount watertight junction Figure 6. box must be mounted with its internal post in the lower left corner as shown in Figure 8. 2. Connect field wiring according to terminal definitions. Figure 7. 3. If the product is not to be installed at this point, use the Back box skirt dust cover to prevent contamination of the wiring termi- model numbers: nals of the mounting plate. BBS-2, BBSW-2, 4. To attach product to mounting plate, hook tabs on the BBSC-2, and BBSCW-2 product housing into the grooves on mounting plate. Then, swing product into position to engage the pins on the product with the terminals on the mounting plate. A0348-00 Make sure that the tabs on the back of the product hous- ing fully engage with the mounting plate. 5. Secure product by tightening the single mounting screw in the front of the product housing.

This manual is also suitable for:

Spectralert advance p2rhSpectralert advance p2rkSpectralert advance p2rhkSpectralert advance p2whSpectralert advance p2wSpectralert advance p4rh ... Show all