System Sensor SpectrAlert Advance Series Installation And Maintenance Instructions

System Sensor SpectrAlert Advance Series Installation And Maintenance Instructions

Selectable output strobes, horns, and horn/strobes

Advertisement

Quick Links

inSTaLLaTion and mainTenanCe inSTruCTionS
Selectable output Strobes, Horns, and Horn/Strobes
For use with the following models: P2R, P2RH, P2RK, P2RHK, P2W, P2WK, P2WH, P2WHK, P4R, P4RH, P4RK, P4W, P4WK, P4WHK, SR, SRH, SRK, SRHK, SW, SWK, SWH, SWHK,
SW-CLR-ALERT, PC2R, PC2RH,PC2RK, PC2RHK, PC2W, PC2WK, PC2WH, PC2WHK, PC4R, PC4RH, PC4W, PC4WK, PC4WHK, SCR, SCRH, SCRK, SCRHK, SCW, SCWK, SCWH,
SCWHK, SCW-CLR-ALERT, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,P2R-P, P2W-P, P2WH-P, P4W-P, SCW-P, PC2R-P, PC2W-P, PC2WH-P, SRK-P, SRHK-P, P2RK-P, P2RHK-P, SWK-P,
SWHK-P, P2WK-P, P2WHK-P, SR-SP, P2R-SP, PC2W-SP, SRK-R, SWK-R, SRHK-R, SWHK-R, P2RK-R, P2WK-R, P2RHK-R, P2WHK-R
NOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof plates
NOTE: When replacing outdoor units; device and back box must be replaced
produCT SpeCiFiCaTionS
Operating Temperature:
Humidity Range:
Strobe Flash Rate:
Nominal Voltage:
Operating Voltage Range (includes fire alarm panels with built in sync):
Operating Voltage with MDL Sync Module:
Input terminal wire gauge:
NOTE : Strobes will operate at 12 V nominal for 15 & 15/75 candela settings only. Switching between ranges is automatic.
dimenSionS For produCTS and aCCeSSorieS
WALL PRODUCTS
Strobes and Horn/Strobes
(including lens)
Horns
SA-WBB Weatherproof Back Box
SA-WBBW Weatherproof Back Box
BBS-2
BBSW-2
Back Box Skirt
mounTing box opTionS
2-Wire Indoor Products
1
4 × 4 × 1
/
, Single Gang, Double Gang, 4˝ Octagon
2
NOTICE: This manual shall be left with the owner/user of this equipment.
generaL deSCripTion
The SpectrAlert Advance series of notification appliances offers a wide range
of horns, strobes, and horn/strobes, for wall and ceiling applications, indoors
and outdoors. They are designed to be used in 12 or 24 volt, DC or FWR
(full wave rectified) systems. These products are electrically backward compat-
ible with the previous generation of SpectrAlert notification appliances. Horn/
strobe products are available in two versions. The 2-wire products fit systems
where a single NAC controls both horn and strobe. The 4-wire products are in-
tended for systems which have separate wiring circuits for the horn and strobe.
All SpectrAlert Advance products are suitable for use in synchronized systems.
The System Sensor MDL module may be used to provide synchronization.
K Series products are designed to be used over a wider range of temperatures
and are suitable for use in wet locations.
Wall and ceiling products may be used interchangeably (wall products may
be used on the ceiling and ceiling products may be used on the wall.)
Fire aLarm SYSTem ConSideraTionS
The National Fire Alarm Code, NFPA 72, requires that all horns, used for
building evacuation produce temporal coded signals. Signals other than those
used for evacuation purposes do not have to produce the temporal coded sig-
nal. System Sensor recommends spacing notification appliances in compli-
ance with NFPA 72.
D690-03-00
Standard Products
K Series
Standard Products
K Series
LENGTH
WIDTH
DEPTH
5.6˝
4.7˝
2.5˝
142 mm
119 mm
64 mm
5.6˝
4.7˝
1.3˝
142 mm
119 mm
33 mm
5.7˝
5.1˝
2.0˝
145 mm
130 mm
51 mm
5.0˝
5.9˝
2.2˝
130 mm
152 mm
57 mm
4-Wire Indoor Products
1
4 × 4 × 1
/
, Double Gang, 4˝ Octagon
2
1
32°F to 120°F (0°C to 49°C)
–40°F to 151°F
10 to 93% Non-condensing
Meets NEMA 4X requirements
1 flash per second
Regulated 12VDC/FWR or regulated 24DC/FWR
8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
9 to 17.5V (12V nominal) or 17 to 33V (24V nominal)
12 to 18 AWG
CEILING PRODUCTS
Strobes and Horn/Strobes
(including lens)
SA-WBBC Weatherproof Back Box
SA-WBBCW Weatherproof Back Box
BBSC-2
BBSCW-2
Back Box Skirt
NOTE: SA-WBB, SA-WBBW, SA-WBBC and SA-WBBCW dimensions
do not include the two mounting tabs
SA-WBB/W (wall), SA-WBBC/CW (ceiling)
Loop deSign and Wiring
The system designer must make sure that the total current drawn by the de-
vices on the loop does not exceed the current capability of the panel supply,
and that the last device on the circuit is operated within its rated voltage.
The current draw information for making these calculations can be found in
the tables within this manual. For convenience and accuracy, use the voltage
drop calculator on the System Sensor website (www.systemsensor.com) or
CD-ROM.
When calculating the voltage available to the last device, it is necessary to
consider the voltage drop due to the resistance of the wire. The thicker the
wire, the smaller the voltage drop. Wire resistance tables can be obtained
from electrical handbooks. Note that if Class A wiring is installed, the wire
length may be up to twice as long as it would be for circuits that are not
fault tolerant.
NOTE: The total number of strobes on a single NAC must not exceed 40 for
24 volt applications or 12 for 12 volt applications. Loop resistance on a single
NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt systems.
For 4-Wire installations, terminals 1, 2, and 3 connect to the strobe; terminals
4 and 5 connect to the horn. The horn and strobe circuits must be wired in-
dependently, and each circuit must be terminated with the appropriate EOL
device. Removal of a notification device will result in an open circuit indica-
tion on the strobe loop.
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
DIAMETER
6.8˝
173 mm
7.1˝
180 mm
7.1˝
180 mm
K Series Products
I56-2769-015R
DEPTH
2.5˝
64 mm
2.0˝
51 mm
2.2˝
57 mm

Advertisement

loading

Summary of Contents for System Sensor SpectrAlert Advance Series

  • Page 1 Loop deSign and Wiring The SpectrAlert Advance series of notification appliances offers a wide range The system designer must make sure that the total current drawn by the de- of horns, strobes, and horn/strobes, for wall and ceiling applications, indoors vices on the loop does not exceed the current capability of the panel supply, and outdoors.
  • Page 2 Figure 1. Wiring 2-Wire produCTS: TabLe 1. STrobe CurrenT draW ( ) For S, SC, p4 & pC4 SerieS: 8–17.5 Volts 16–33 Volts INPUT Candela FROM OUTPUT FACP Standard Candela Range NEXT 15/75 PRIOR DEVICE DEVICE OR EOL – – High Candela Range A0367-01 Figure 2.
  • Page 3 TabLe 4. 2-Wire Horn/STrobe CurrenT draW ( ) For p2 and pC2 STandard CandeLa SerieS: 8–17.5 Volts 16–33 Volts DC Input 15 cd 15/75 cd 15 cd 15/75 cd 30 cd 75 cd 95 cd 110 cd 115 cd Temporal High Temporal Medium Temporal Low Non-temporal High...
  • Page 4 The strobe must have an uninterrupted source of power in order hearing the alarm. The horn may not be heard by persons who are hearing impaired. to operate correctly. System Sensor recommends that the horn and signal strobe always NOTE: Strobes must be powered continuously for horn operation.