Figure 2-8 Rectifier
(1) Run indicator
(4) Locking latch
Table 2-1 Rectifier indicator description
Indicator
Run indicator
Alarm indicator
Fault indicator
Issue 02 (2019-02-26)
(2) Alarm indicator
(5) Handle
Color
Status
Green
Steady on
Off
Blinking
at 0.5 Hz
Blinking
at 4 Hz
Yellow
Off
Steady on
Blinking
at 0.5 Hz
Red
Off
Steady on
Copyright © Huawei Technologies Co., Ltd.
(3) Fault indicator
Description
The rectifier has an AC power input.
The rectifier has no AC power input.
The rectifier is faulty.
The rectifier is being queried.
The rectifier is loading an application
program.
No alarm has been generated.
The rectifier has generated an alarm due
to ambient overtemperature.
The rectifier has generated an alarm for
shutdown due to ambient overtemperature
or undertemperature.
The rectifier is protecting itself against AC
input overvoltage or undervoltage.
The rectifier is hibernating.
The communication between the rectifier and
the SMU has been interrupted.
The rectifier is running properly.
The rectifier has been locked out due to
output overvoltage.