Texmate Tiger 320 Series User's Manual Supplement

Texmate Tiger 320 Series User's Manual Supplement

Totalizing & batching
Hide thumbs Also See for Tiger 320 Series:

Advertisement

T T i i g g e e r r 3 3 2 2 0 0 S S e e r r i i e e s s
Associated Documents
The following documents must be read
together with this supplement:
Relevant Tiger 320 Series User Manual
The user manual provides general informa-
tion on the relevant Tiger 320 Series meter.
Tiger 320 Series Programming Code Sheet
The programming code sheet provides all
meter programming codes including set-
point programming codes.
Analog Output Module Supplement
This supplement provides detailed descrip-
tions of the analog output module.
This document was written using Tiger
320 Series Code Version 3.02n.
The totalizer for earlier versions of code
may differ to that shown.
Consult your Programming Code Sheet
(NZ101) for relevant totalizer settings.
Programming Tip
This document has been written
using a DI-50 7-segment, 5-digit
display meter. When program-
ming meters with other display
options, some display readings
may vary to the diagrams shown.
Note
It is assumed that you are famil-
iar with the Programming
Conventions used throughout
the range of Texmate Tiger 320
Series literature as described in
the user manual.
• Totalizing Supplement (NZ208)
TOTALIZING & BATCHING SUPPLEMENT
This document is designed to supplement the information described in
the Tiger 320 Series user manual. It covers the meter's Totalizing and
Batching Functions.
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Before You Start Setting the Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Totalizer Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
How it all Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Configuring the Meter as a Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Totalizer Programming Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Input Signal Display Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Totalizer Display Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Resetting the Total . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Pulse Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Meter Programming Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Totalizer Configuration Programming Codes . . . . . . . . . . . . . . . . . . . . . . .13
Totalizer Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Example 1 - Totalizing a Single Volume Input . . . . . . . . . . . . . . . . . . . . . .16
Example 2 - Advanced Totalizing of a Flow Input . . . . . . . . . . . . . . . . . . .18
Programming Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Standard Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Configure Data Source Procedure - For Example 2 . . . . . . . . . . . . . . . . .25
Two-point Calibration - For Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Configure Pulse Output Procedure - For Example 2 . . . . . . . . . . . . . . . . .31
Configure Analog Output Procedure - For Example 2 . . . . . . . . . . . . . . . .33
Local Distributor Address............. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

List of Figures

Figure 1 - Decimal Point Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Figure 2 - Resetting the Total . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Figure 4 - Pulse Output from Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Figure 5 - Programming Code List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Figure 6 - Totalizing a Single Volume Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 7 - Advanced Totalizing Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 8 - Multimeter to Meter Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com
Contents
Contents
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Tiger 320 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Texmate Tiger 320 Series

  • Page 1: Table Of Contents

    TOTALIZING & BATCHING SUPPLEMENT This document is designed to supplement the information described in Associated Documents the Tiger 320 Series user manual. It covers the meter’s Totalizing and Batching Functions. The following documents must be read together with this supplement:...
  • Page 2 Meter – Controller The term meter, as used throughout this document, is a generic term for all Tiger 320 Series signal processors and controllers Error Message...
  • Page 3: Technical Description

    A customer has a settling tank being filled with water. The flow rate is metered and input to a Tiger 320 Series meter. The flow rate indicates the speed at which the volume of water travels past a set point, but not the total volume accumulated in the tank. The meter’s totalizer performs this function and provides the customer with the total amount...
  • Page 4: Totalizer Settings

    1, we would set it to 10. The 1,000 gallons would then display as 1.0 on the total- izer as long as the input signal resolution is set to 0.1 (tenths). Page 4 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 5: How It All Works

    (GPM) to total volume. The customer requires the flow rate to display directly in GPM and the total volume to display in hundredths of a kilogallon (0.01 of a kilogallon). Texmate installed a Tiger 320 Series DI-50 meter and calibrated the input for a full scale range of 1,500 GPM.
  • Page 6 (energy/time) kilowatts into energy in units of megawatt hours using a totalizer. Texmate installed a Tiger 320 Series DI-50 meter with a single phase power module and cal- ibrated the input for a full scale range of 200 kW. The meter is configured to display the power (input) reading in tenths of a kilowatt (0.1 kW) on the operational display, and the energy...
  • Page 7 CUTOFF Set to Not a mandatory setting 10 hours. Can be anywhere between –19999 to 32767. 1 day. 1 week. ROLLOVER Set to • Totalizing Supplement (NZ208) • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 7...
  • Page 8: Configuring The Meter As A Totalizer

    (see Figure 1). Configuring the decimal point can produce the following display resolutions: • One hundred thousandths (9.99999)(6 or 8-digit display only). • Ten thousandths (99.9999). • Thousandths (999.999). • Hundredths (9999.99). • Tenths (99999.9). • One (999999). Page 8 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 9: Totalizer Display Configuration

    The most commonly used calibration method is the two-point calibration mode. This method requires an input signal source that covers the input signal’s high and low limits. • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 9...
  • Page 10: Resetting The Total

    Scaling Parameters Tiger 320 Series meters use 5, 6, or 8-digit displays. The range of a 5-digit display is –19999 to 99999 counts on the display, providing a total range of 120,000 counts. The range of a 6- digit display is –199999 to 999999 counts on the display, providing a total range of 1,200,00 counts.
  • Page 11: Analog Output

    See Example 2 – Advanced Totalizing of a Flow Input for full details on configuring the ana- log output module. See Analog Output Module Supplement (NZ200) for further information on configuring the analog output module. • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 11...
  • Page 12: Meter Programming Codes

    Operational Display display at any point, press the button once. Then press the button at Prog. the same time to exit. Figure 5 – Programming Code List Page 12 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 13: Totalizer Configuration Programming Codes

    • 1 day. total from 1 to 65535 Cutoff from –19999 to 32767 • 1 week. buttons to set Rollover to ON or OFF • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 13...
  • Page 14 To leave the cycle, the Code 1 digits must be reset to any relevant func- tion between [X00] to [X20]. This takes you into Code 2. Page 14 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 15 0.0/0.001 to 6553.5/65.353 secs 6553.5/65.353 secs SP1/SP2 ONLY Repeat OFF Mode Multiple Actuation Resolution setting Off-time (oFF_t) 0.0/0.001 on_t 0.0/0.001 to applies to to 6553.5/65.353 secs 6553.5/65.353 secs SP1/SP2 ONLY • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 15...
  • Page 16: Totalizer Examples

    Figure 6 – Totalizing a Single Volume Input Configuration Settings To perform as our customer requires in this example, the input signal channel and totalizer must be configured with the following settings: Page 16 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 17 10 hours. CUTOFF Set to 0 1 day. 1 week. ROLLOVER Set to to reset the totalizer to 0 when it reaches 999.99 kiloliters • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 17...
  • Page 18: Example 2 - Advanced Totalizing Of A Flow Input

    Press the UP button 6 times to enter the display view mode and view Totalizer 1. To View Totalizer 2: Press the DOWN button once after viewing the Totalizer 1 recall display to enter the display view mode and view Totalizer 2. Page 18 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 19: Configuration Settings

    • Set the required total to: 3 Totalizer 2 displays 1 every 10,000 gal- lons recorded by totalizer 1 • Cut Off: 0 • Rollover = ON • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 19...
  • Page 20 1 day. CUTOFF Set to 1 week. ROLLOVER Set to Select OFF as we are using a setpoint to reset totalizer 1 Page 20 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 21 And select the following reset settings: See Configure Setpoint and Relay Settings Procedure RESET TRIGGER: MAKE (Reset to 0.0) RESET DESTINATION REGISTER: tot_1 (Total 1) RESET MODE: I–S+C RESET CONSTANT: REMAINING SETTINGS: • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 21...
  • Page 22 See Configure Analog Output Procedure CAL LOW: 4 mA CAL HIGH: 20 mA See also Analog Output Module Supplement (NZ200) for full details to configure the meter for analog output. Page 22 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 23: Programming Procedures

    (the 3rd selects totalizer 1 or 2). See Configure Totalizer Settings Procedure on Page 29 for an example. This procedure uses the set up for totalizer 1 in Example 2 as an example. • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 23...
  • Page 24 The analog output is active when the selection header is in the correct position, the selected analog output (1 or 2) is scaled and calibrated, and the data source has been selected. Page 24 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 25: Configure Data Source Procedure - For Example 2

    With bargraph meters the from the options listed in the Select PRIMARY display is the digital display, and the SECONDARY display is the Data Source diagram above. bargraph display. • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 25...
  • Page 26: Configure Display Format Mode Procedure - For Example 2

    Display Format Mode diagram above: 1st Digit = 0 No rounding 2nd Digit = 0 Decimal display 3rd Digit = 6 Decimal point setting X.X Page 26 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 27: Two-Point Calibration - For Example 2

    TEXMATE Prog. Step 6 Set reading for zero Prog. Press load into meter and enter span mode Operational Display To Step 7 • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 27...
  • Page 28: Input Signal Filtering And Averaging - For Example 2

    1 to 255 samples Exit Code 1 and return TEXMATE to operational display Example Step TEXMATE Step 6 Prog. Save averaging Prog. sampling rate setting Press Operational Display Page 28 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 29: Configure Totalizer Settings Procedure - For Example 2

    Step Configure Totalizer Settings Step 12 Press Prog. Step 6 Procedure Enter the rollover mode continued on next page (Step 13). Enter the running Press time mode • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 29...
  • Page 30 TEXMATE Prog. TEXMATE Step 15 Press at same Exit Code 1 and return to Prog. time the Operational Display Press at same time TEXMATE Prog. Operational Display Page 30 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 31: Configure Pulse Output Procedure - For Example 2

    Step 13 Configure Pulse Press Output Procedure Prog. continued on next page TEXMATE Step Step 6 Prog. Select Total 1 as the source of data for SP1 • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 31...
  • Page 32 Prog. Step 17 Press Ensure print trigger is set to [oFF] TEXMATE Prog. TEXMATE To Step Step 18 Prog. Ensure log trigger is set to [oFF] Press Page 32 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 33: Configure Analog Output Procedure - For Example 2

    Steps 1 to 8 describe how to set the zero [ZEro] and full scale [F_SCL] parameters. Steps 9 to 19 describe how to calibrate the meter’s analog output mA/V low [CAL_L] and high [CAL_h] settings. • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 33...
  • Page 34 If not 0.0, adjust the low analog output signal counts to 0.0 TEXMATE Example Step 6 Prog. Save zero setting Press and enter full scale To Step 7 setting mode Page 34 Texmate Inc. Tel. (760) 598-9899 • www.texmate.com • Totalizing Supplement (NZ208)
  • Page 35 Exit Code 1 and return signal setting. Enter analog time to operational display TEXMATE output high signal calibration To Step mode TEXMATE Prog. TEXMATE Prog. Operational Display Prog. • Totalizing Supplement (NZ208) Texmate, Inc. Tel. (760) 598-9899 • www.texmate.com Page 35...
  • Page 36: Local Distributor Address

    Texmate has facilities in the USA, Japan, New Zealand, Taiwan, and Thailand. We also have authorized distributors throughout the USA and in 28 other countries. 995 Park Center Drive • Vista, CA 92083-8397 1934 Kellogg Ave.,Carlsbad, CA 92008 For ordering info call: ..1-800-TEXMATE (1-800-839-6283) For tech assistance call: .