Mitsubishi Electric Melsec-k Instruction Manual page 74

Optical data link system
Hide thumbs Also See for Melsec-k:
Table of Contents

Advertisement

I
,
Mode
[
5. OPERATING PROCEDURE
llilELEEEaK
Description
(2)
Slave test
Unit Type
1
Name
KJ7 1 P3,
KJ72P5
KOJl P
L
Slave
test
Used to allow the sending and receiving
functions of i t s own channel to be
tested
by
the mating channel. By setting
the mating channel to master test mode
and operating the RESET switch on slave
test side and then the
RESET
switch on
the master test side, the built-in test
program
is
started.
Normal
8
LEDs a t right
row on the front
flicker.
ERROR
LED
f I ickers.
Slave channel
Master channel
1
I
k
I \
I
Link unit
0
Software intervention
I
Mode
3
Mode
2
LED
of
corres-
ponding error i s lit.
Check the content
of
error by moni-
toring D126.
I
Fig.
5.7 Slave
Test
Cautions for master and slave tests
1) Before making the tests, move the RUN switch of programmable controller to the STOP po-
si tion.
2)
When the KJ71P3 is used, perform reset operation by use of the RESET switch of CPU in i t s
own channel.
3) When the system to be tested consists of 3 or more channels, be sure to set the channels, which
are not put to the master and slave tests, to the offline mode.
73