NOTE: Controller and device configurations are not nec-
essarily limited to three devices, but the total
power draw, including accessories, cannot exceed
CONNECT POWER TO
TERMINALS 1 AND 2
120/240
VAC
TRANSFORMER
Fig. 6. Power wiring details for two or more controllers and devices per transformer.

Communications

Sylk
Bus
Sylk is a two wire, polarity insensitive bus that provides
both 18 VDC power and communications between a Sylk-
enabled sensor, Sylk-enabled device, and a Sylk-enabled
controller. Using Sylk-enabled sensors and devices saves
I/O on the controller and is faster and cheaper to install
since only two wires are needed and the bus is polarity
insensitive. Sylk sensors and devices are configured using
the latest release of the Spyder Tool for WEBPro and
WEBStation. Using 18 AWG wire, the maximum wire
length for Sylk is 200 ft.
For Spyders and Sylk IO devices, use the Resource Usage
View in the Spyder tool to determine the maximum
number of devices.

Setting the Device Bus Address Dial

Each device on a Sylk bus must use a different bus
address, and there may be multiple Sylk IOs wired on a
single Sylk bus. To change the bus address of a device,
adjust the address dipswitches to match that of the
desired bus address (1–15). Use the bus address label,
shown in Fig. 7, as a reference. The default address for
Sylk IOs is 1. The address on the device must match the
address in the configuration tool.
2 2 2 2 2 2 2 2 3
2
3
3
3
3
1 2 3 4 5 6 7 8 0
9
1 2 3 4 5 6 7 8 0
1 1 1 1 1 1 1 1 2
1
1 2 3 4 5 6 7 8
9
0
1
2 3 4 5 6 7 8 0
EARTH
GROUND
(TERMINAL 3)
COM
24 VAC
OUTPUT
DEVICE
POWER
100 VA when powered by the same transformer
(U.S. only). For power wiring recommendations,
see "Power" on page 3.
3
3
3
3 4
3
1 1 1 1 1 1 2 2 2
1
2
2
9
3 4 5 6 7 8 9 0 2
1
3 4
1
1 1
1
9
1
2
3
4 5 6 7 8 9 0 2
1
EARTH
GROUND
(TERMINAL 3)
Fig. 7. Bus address settings.

Wiring Method

WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring,
or making wiring connections, to prevent electrical
shock or equipment damage.
NOTE: When attaching two or more wires to the same
terminal, other than 14 AWG (2.0 sq mm), be
sure to twist them together. Deviation from this
rule can result in improper electrical contact (see
Fig. 8).
Each terminal can accommodate the following gauges of
wire:
— Single wire: from 22 AWG to 14 AWG solid or stranded
7
SYLK™ I/O DEVICES
1 1 1 1 1 1 2 2 2
1
2
2
3 4 5 6 7 8 9 0 2
1
3 4
1 1
1
1
2
3
4 5 6 7 8 9 0 2
1
EARTH
GROUND
(TERMINAL 3)
M35143
M35180
31-00028—02