Table 4: Additional PW7000 Input Module LEDs
LED number
D3
D4
D5
D6
D7
D8
D9
D10
D11
D12
D13
D14
D15
D16
D17
D18
D19
D20
D21
D22

Power

The Input Board accepts 12VDC with an operating range of 10 to 14VDC and con-
sumes 250mA of current. Locate power source as close to this board as possible.
Connect power with minimum of 18AWG wire.
Note: POLARITY for 12VDC power is important. Make sure the +12 VDC is connected to the
terminal labeled +12V and the return is connected to the terminal labeled GND.

Communications

The Input Board communicates to the host controller through an RS-485 inter-
face.The interface allows for multi-drop communication of up to 4,000 feet (1,200
m) total per port. Use two twisted pair (minimum 24AWG) with shield for communi-
cation (Belden 9842 or equiv.). The default speed of this port is 38.4Kbps but it can
be downgraded to 19.2Kbps or 9.6Kbps if the line conditions or receiving equip-
ment require it (see
jumper settings and
for DIP switch settings).
PW-7000 Input Module (PW7K1IN) Installation Guide, Document 800-25674V1
Description
Input 0 status
Input 1 status
Input 2 status
Input 3 status
Input 4 status
Input 5 status
Input 6 status
Input 7 status
Input 8 status
Input 9 status
Input 10 status
Input 11 status
Input 12 status
Input 13 status
Input 14 status
Input 15 status
Tamper status
Power status
Relay 0 status
Relay 1 status
Table 1: PW-7000 Input Module Jumper Settings
Table 2: PW-7000 Input Module DIP Switch Settings
(page 11) for
(page 11)
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pw7k1in

Table of Contents