Checkout; Check Installation And Wiring - Honeywell Sylk SI06042 Product Data

I/o devices
Table of Contents

Advertisement

Table 6. Description of wiring terminal connections for
SIO12000. (Continued)
SIO1200
0
Terminal
s
Label
12
UI-4
Universal Input
13
UI-12
Universal Input
14
COM
UI COMMON
15
UI-11
Universal Input
16
UI-10
Universal Input
17
COM
UI COMMON
18
UI-9
Universal Input
19
UI-8
Universal Input
20
COM
UI COMMON
21
UI-7
Universal Input
22
UI-6
Universal Input
23
COM
UI COMMON
24
UI-5
Universal Input
Table 7. Description of wiring terminal connections for
SIO6042.
SIO6042
Terminal
s
Label
1
24VAC
2
24VAC COM 24VAC-COMMON
3
EGND
4
N/A
5
S-BUS
6
S-BUS
7
UI-1
8
COM
9
UI-2
10
DO-1
11
COM
12
DO-2
13
AO-4
14
COM
15
AO-3
16
AO-2
17
COM
18
AO-1
Connection
Connection
24VAC Power
Chassis/Earth Ground
Not Applicable
Sylk
Sylk
Universal Input
UI COMMON
Universal Input
Discrete Triac Output
DO COMMON
Discrete Triac Output
Analog Output
AO COMMON
Analog Output
Analog Output
AO COMMON
Analog Output
Table 7. Description of wiring terminal connections for
SIO6042
Terminal
s
Label
19
UI-6
20
COM
21
UI-5
22
UI-4
23
COM
24
UI-3
IMPORTANT
If the device is not connected to a good earth
ground, the device's internal transient protection
circuitry is compromised and the function of
protecting the device from noise and power line
spikes cannot be fulfilled. This could result in a
damaged circuit board and require replacement of
the device. Refer to installation diagrams for
specific wiring.

CHECKOUT

Step 1. Check Installation and Wiring
Inspect all wiring connections at the device terminals, and
verify compliance with installation wiring diagrams. If any
wiring changes are required, first be sure to remove power
from the controller before starting work. Pay particular
attention to:
— 24 Vac power connections. Verify that multiple devices
being powered by the same transformer are wired with
the transformer secondary connected to the same
input terminal numbers on each device. Use a meter to
measure 24 Vac at the appropriate terminals (see Fig. 6
on page 7). Device configurations are not necessarily
limited to three devices, but the total power draw,
including accessories, cannot exceed 100 VA when
powered by the same transformer (U.S. only).
— Be sure that each device has terminal 3 wired to a
verified earth ground, using a wire run as short as
possible with the heaviest gauge wire available, up to
14 AWG (2.0 sq mm) with a minimum of 18 AWG (1.0 sq
mm) for each controller in the group (see Fig. 6 on
page 7).
— Verify that Triac wiring of the digital outputs to external
devices uses the proper load power and 24 Vac
common terminal (digital output common terminals)
for High-Side switching.
NOTE: All wiring must comply with applicable electrical
codes and ordinances or as specified on installa-
tion wiring diagrams.
For guidelines for wiring run lengths and power budget,
see "Power" on page 3.
9
SYLK™ I/O DEVICES
SIO6042.
Connection
Universal Input
UI COMMON
Universal Input
Universal Input
UI COMMON
Universal Input
31-00028—02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sylk si04022Sylk si012000