ML7984 Wiring
SIGNAL
SOURCE
3 ML7984
R
W
C
3 ML7984 2
R
W
C
3 ML7984 2
R
W
C
FIG. 8 — ML7984 WIRING WITH 10
VDC ANALOG CONTROL SIGNAL
FUNCTION
DIP SWITCH CONFIGURATION
1000
2-10 Vdc Direct Acting
1010
10-2 Vdc Reverse Acting
For Figures 8 and 9 the following apply:
Allow 0.5 amps maximum for each device. Actuators and controller can share same transformer providing
1
the VA rating of the transformer is not exceeded and proper phasing is observed.
"T5" and "W" terminals are factory connected internally. Device is compatible with the 3-wire control system.
2
Use configuration DIP switches to select device functions: Direct acting function ( actuator stem moves
3
upwards with signal increases ) or Reverse acting function ( actuator stem moves downwards with signal
increases ).
NOTE:
Always turn power off before setting the DIP switches.
2
T6
T5
1
T6
24 Vac
T5
OR
T6
28 Vdc
T5
T6
T5
On (1)
Off (0)
1
2
3
4
On (1)
Off (0)
1
2
3
4
SIGNAL
SOURCE
L1
L2
+
FIG. 9 — ML7984 WIRING WITH 20mA
ANALOG CONTROL SIGNAL
FUNCTION
X000
4-20 mA Direct Acting
X010
20-4 mA Reverse Acting
6
3 ML7984
2
R
T6
W
T5
C
3 ML7984 2
R
T6
24 Vac
W
T5
C
3
ML7984
2
(SLAVE)
R
T6
W
T5
C
DIP SWITCH CONFIGURATION
Master actuator
Slave actuator
1
1
Master actuator
Slave actuator
1
1
1
L1
L2
OR
+
T6
28 Vdc
T5
2
3
4
On (1)
Off (0)
2
3
4