Daikin R-22 Refrigerant Piping Design Manual page 70

Commercial air conditioning systems
Hide thumbs Also See for R-22:
Table of Contents

Advertisement

Figure 29: R-22 Suction Gas Velocity – SI
Figure 29
is based on 4.4°C suction temperature and 41°C condensing temperature. For other conditions, apply correction factors
from
Table
50.
Table 50: R-22 Suction Gas Velocity Correction Factors – SI
Condenser
Temp (°C)
-12 .2
29.5
1.63
32.2
1.67
35.0
1.71
37.8
1.75
40.6
1.79
43.4
1.84
46.1
1.89
48.9
1.94
51.7
1.99
54.5
2.05
57.3
2.12
60.0
2.19
62.8
2.27
AG 31-011 • REFRIGERANT PIPING DESIGN
-9 .4
-6 .7
-3 .9
1.48
1.34
1.21
1.51
1.37
1.24
1.54
1.40
1.27
1.58
1.43
1.30
1.62
1.46
1.33
1.66
1.50
1.36
1.70
1.54
1.39
1.75
1.58
1.43
1.80
1.63
1.47
1.85
1.67
1.52
1.91
1.73
1.56
1.97
1.78
1.61
2.04
1.84
1.67
Suction Temperature (°C)
-1 .1
1 .7
1.10
1.00
1.13
1.02
1.15
1.05
1.18
1.07
1.20
1.10
1.24
1.12
1.27
1.15
1.30
1.18
1.34
1.22
1.38
1.25
1.42
1.29
1.46
1.33
1.51
1.37
70
4 .5
7 .2
10 .0
0.92
0.84
0.76
0.93
0.85
0.78
0.95
0.87
0.80
0.98
0.89
0.82
1.00
0.91
0.83
1.02
0.94
0.86
1.05
0.96
0.88
1.08
0.98
0.90
1.11
1.01
0.92
1.14
1.04
0.95
1.17
1.07
0.98
1.21
1.10
1.01
1.25
1.14
1.04
www.DaikinApplied.com