PV Grid Tie Inverter SOLTARO Three Phase Inverter Installation and Operation Manual Soltaro Pty Ltd 1/21 Hugo Place Mansfield QLD 4122, Australia Please record the serial number of your inverter and quote this when you contact us. Soltaro Pty Ltd...
1. Introduction ………………………………… 6.3.2 Set Address SOLTARO three phase series PV inverters could transfer DC power from PV panels into AC power and feed into grid. There are 6 models for SOLTARO three phase inverter. …………… 6.4 Advanced Info - Technicians Only SOLTARO-3P5K,SOLTARO-6K, SOLTARO-10K, SOLTARO-15K are used for 380/400V 6.4.1 Alarm Message...
Please don’t connect PV array positive(+) or negative(-) to the ground, it could Locking screws cause serious damage to the inverter. AC connector DC connectors 4 pairs(2 for SOLTARO-6K) WARNING: Manual Electrical installations must be done in accordance with the local and national electrical safety standards...
To reduce the risk of fire, branch-circuit over-current protective devices (OCPD) are required for circuits connected to the Inverter. The recommend rated trip current for AC breaker should be 25A for SOLTARO-3P5K,SOLTARO-6K inverter, 32A for SOLTARO-10K, SOLTARO-15K, SOLTARO-20K-HV inverter. CAUTION: Risk of electric shock.
Exposure to direct sunlight will increase the operational temperature of the inverter and Access to modify the adjustable settings (the ESC and ENTER keys). may cause output power limiting. SOLTARO recommends inverter installed to avoid direct sunlight or raining. 3.4 LCD To avoid over heating ambient air temperature MUST be considered when choosing the inverter installation location.
4. Installation 4. Installation 4.2 Mounting the Inverter Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may Please use suitable fixings for wall type (e.g. use dynabolts for brick, masonry, etc). result in less than expected output power.
Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter Maximum 1000Voc for Inverter SOLTARO-3P5K SOLTARO-6K SOLTARO-10K SOLTARO-15K SOLTARO-20K-HV Please don’t connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter Figure 4.4 Wall Mount Bracket...
4. Installation 4. Installation The steps to assemble the DC connectors are listed as follows: I) Strip off the DC wire for about 7mm, Disassemble the connector cap nut (see Figure 4.7). Figure 4.10 Connector with Cap nut Screwed on v) Then connect the DC connectors to the inverter.
4. Installation 4. Installation Each SOLTARO three phase inverter is supplied with an AC grid terminal connector, which is b) Assemble the connector and tighten up cap on the terminal (as shown in Figure 4.14). in Figure 4.12. Figure 4.15 Tighten up the cap on the terminal Figure 4.12 AC Grid Terminal Connector...
4. Installation 5. Start & Stop 5. Inverter monitoring Connection. 5.1 Start the Inverter The inverter can be monitored by Wi-Fi or GPRS functions. All the communication functions are optional (Figure 4.18), please refer to communication connection instructions. To start up the Inverter, it is important that the following steps are strictly followed: For inverter connect with DRM, please connect communication cable or device to DRM COMM port.
6.2 Information Table 6.1 Information Indicator The SOLTARO three phase PV inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
The display shows the 100 latest alarm messages (see Figure 7.6). Screens can be scrolled The default address number of SOLTARO three phase inverter is “01”. manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous YES=<ENT>...
6. Operation 6. Operation 6.4.2 Running Message 2015-02: 0510kWh 2015: 0017513kWh 2015-01: 0610kWh 2014: 0165879kWh This function is for maintenance personnel to get running message such as internal temperature, Standard NO. etc. Figure 6.12 Month energy Figure 6.13 Yearly energy Screens can be scrolled manually by pressing the UP/DOWN keys.
6. Operation 6. Operation NOTE: 6.5 Advanced Settings - Technicians Only The " User-Def" function can be only used by the service engineer and must be allowed by the local energy supplier. NOTE: Access to this area is for fully qualified and accredited technicians only. Below is the setting range for “User-Def”.
6. Operation 6. Operation 6.5.4 New Password 6.5.7 Special settings This function is applicable by maintenance personnel only. YES=<ENT> NO=<ESC> Password: 0000 Special settings have the submenu shown below: Figure 6.19 Set new password 1. Grid Filter Set 2. Relay_Protect Set 3.
Page 17
6. Operation 6.5.8.1 Working Mode Set 5. Volt-Var SOLTARO SOLTARO inverter support 6 working mode in this menu: Set Voltage1: 207-220V, Default 207V 1. Null 2. Volt-watt 3. Volt-Var 4. Fixed-PF 5. Reac-Power 6. Power-PF Set Voltage2: 216-230V, Default 220V...
6. Operation 6. Operation 6.5.8.2 Power Rate Limit 6.5.8.4 10mins Voltage Set This function is used for change Power Ramp-up rate. When inverter start up or input string Thisfunctionisusedforsetting10minsVoltage,thescreenisshownasbelow. MPPT changes, inverter power ramp-up rate is limited in this menu. YES=<ENT>...
6. Operation 7. Maintenance SOLTARO three phase inverter does not require any regular maintenance. However, clean HMI Updater have the submenu shown below: the heat-sink will help inverter dissipating heat and increase the life time of inverter. HMI Current Ver.: 02 The dirt on the inverter can be cleaned with a soft brush.
Page 20
8. Trouble Shooting 8. Trouble Shooting Alarms Cause Solution Alarms Cause Solution Test – DC switch OFF Test – DC switch OFF • Check frequency at the inverter test points • Check PV connections • If Frequency measures high, adjust upper •...
Page 21
8. Trouble Shooting 8. Trouble Shooting NOTE: Alarms Cause Solution If the inverter displays any alarm message as listed in Table 8.1; please Test – With DC Switch OFF turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5 •...
9. Specifications 9. Specifications Model SOLTARO-3P5K Model SOLTARO-6K SOLTARO-10K The max DC input voltage The max DC input voltage 1000Vdc 1000Vdc MPPT operation range MPPT operation range 200~800Vdc 200~800Vdc The max dc input current The max dc input current 15+15Adc...
Page 23
9. Specifications 9. Specifications SOLTARO-15K Model SOLTARO-20K-HV Model SOLTARO-6K-LV The max DC input voltage The max DC input voltage 600Vdc 1000Vdc MPPT operation range MPPT operation range 150~500Vdc 200~800Vdc The max dc input current The max dc input current 15+15Adc...
Page 24
9. Specifications Model SOLTARO-10K-LV The max DC input voltage 600Vdc MPPT operation range 150~500Vdc The max dc input current 18+18Adc Number of MPPT/strings per MPPT Rated output power 10kW The transient max power 10kW Rated grid voltage 208/220/240Vac The grid voltage range 180~270Vac(adjustable)