Tc 4 - Honeywell TC Series Technical Information

Tightness controls, adjustable test period which can be adapted to different systems, adjustable test instant allows quick system start, maximum safety thanks to self-monitoring electronics
Table of Contents

Advertisement

Technical data
Mechanical data
Length of connection cable:
at 230 V AC/120 V AC: any,
at 24 V DC (supply connected to PE):
max. 10 m permitted,
at 24 V DC (supply not connected to PE):
any.
Cable cross-section: min. 0.75 mm
max. 2.5 mm
2
(AWG 14).
5 cable glands: M16 x 1.5.
Valve opening time: 3 s.
Housing made of impact-resistant plastic.
Connectors: aluminium.
Enclosure: IP 65.
Weight:
TC 1V: 215 g (0.47 lbs),
TC 1C with adapter: 260 g (0.57 lbs),
TC 2 with adapter: 260 g (0.57 lbs),
TC 3: 420 g (0.92 lbs).
TC · Edition 08.17
2
(AWG 19),

7 .2 TC 4

Electrical data
Mains voltage:
110/120 V AC, -15/+10%, 50/60 Hz,
220/240 V AC, -15/+10%, 50/60 Hz,
24 V DC, ±20%.
Power consumption:
10 VA for 110/120 V AC and 220/240 V AC,
1.2 W for 24 V DC.
Fusing: fine-wire fuse 5 A, slow-acting, H pursuant to
IEC 127, also protects the valve outputs and external
operating signal.
Switching current for valves/enable output: max. 5 A.
External operating signal: with mains voltage, max. 5 A
resistive load (UL listed: 5 A for 120 V), max. 2 A at
cos ϕ = 0.35 (pilot duty).
Fault output: dry contact (not internally fused),
max. 1 A for 220/240 V (high voltage: 264 V),
max. 2 A for 120 V.
Reset: using a button on the device.
Remote reset: by applying control voltage (terminal 5).
44

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tc 1Tc 1vTc 1cTc 2Tc 3Tc 4

Table of Contents