Accessories; Socket; Valve Connection Cable; External Pressure Switch For Tc 4 - Honeywell TC Series Technical Information

Tightness controls, adjustable test period which can be adapted to different systems, adjustable test instant allows quick system start, maximum safety thanks to self-monitoring electronics
Table of Contents

Advertisement

Accessories

6 Accessories

6 .1 Socket

Standard socket, 3 pins + PE, black/B:
Order No. 74916715

6 .2 Valve connection cable

Standard socket, 3 pins + PE, black,
4-core electrical cable, cable length 0.45 m, Order
No. 74960689
TC · Edition 08.17

6 .3 External pressure switch for TC 4

DG
Gas pressure switches DG, DG..C for monitoring the
pressure between the valves to be checked.
For inlet pressures of 0.5 to 500 mbar (0.2 to 195 "WC).
The switching differential may not exceed ±10% of the
set switching pressure
(see Technical Information bulletin Pressure switch for
gas DG, DG..C at www.docuthek.com).
Adjustment
The external pressure switch is set to half the inlet pres-
sure p
/2 (only NO contact required) in order to check
u
both valves with equal sensitivity.
Example: p
= 100 mbar (39 "WC),
u
set switching pressure p
DG..C
/2 = 50 mbar (19.5 "WC).
u