Function
Test procedure B
Valve V2 opens for the opening time t
again. During the measurement time t
control checks the pressure p
If pressure p
> p
/2, valve V1 is leaking.
z
u
If pressure p
< p
/2, valve V1 is tight. Valve V1 is
z
u
opened for the set opening time t
During the measurement time t
checks the pressure p
z
If pressure p
< p
/2, valve V2 is leaking.
z
u
If pressure p
> p
/2, valve V2 is tight.
z
u
The tightness test can only be performed if the pres-
sure downstream of V2 is around atmospheric pressure
and the volume downstream of V2 is at least 5 x higher
than the volume between the valves.
If the power fails briefly during the test or during opera-
tion, the TC will restart in accordance with the test pro-
cedure described above.
If there is a fault message, the fault is displayed again
after a power failure.