Honeywell TC Series Technical Information page 23

Tightness controls, adjustable test period which can be adapted to different systems, adjustable test instant allows quick system start, maximum safety thanks to self-monitoring electronics
Table of Contents

Advertisement

Function
Test procedure B
Valve V2 opens for the opening time t
again. During the measurement time t
control checks the pressure p
If pressure p
> p
/2, valve V1 is leaking.
z
u
If pressure p
< p
/2, valve V1 is tight. Valve V1 is
z
u
opened for the set opening time t
During the measurement time t
checks the pressure p
z
If pressure p
< p
/2, valve V2 is leaking.
z
u
If pressure p
> p
/2, valve V2 is tight.
z
u
The tightness test can only be performed if the pres-
sure downstream of V2 is around atmospheric pressure
and the volume downstream of V2 is at least 5 x higher
than the volume between the valves.
If the power fails briefly during the test or during opera-
tion, the TC will restart in accordance with the test pro-
cedure described above.
If there is a fault message, the fault is displayed again
after a power failure.
TC · Edition 08.17
= 3 s and closes
L
, the tightness
M
between the valves.
z
. V1 closes again.
L
, the tightness control
M
between the valves.
V1
V2
p
p
u
z
START
Test procedure A
+
p
>
z
V1
t
= 3 s
L
V1
t
M
p
u
p
>
z
2
+
V2
OK
V2
V2
t
= 3 s
L
V2
t
M
+
p
u
p
>
z
2
V1
OK
V1
TEST
Test procedure B
p
u
2
V2
t
= 3 s
L
V2
t
M
+
p
u
p
>
z
2
V1
V1
OK
V1
t
= 3 s
L
V1
t
M
p
u
p
>
z
2
+
V2
V2
OK
23