Diagnostics for stream refrigeration compressors
Hide thumbs Also See for CoreSense:
Table of Contents

Advertisement

Technical Information
Flash
Alarm conditions
code
8
Trip: Appears when there is a low
Low voltage
compressor voltage.
9
Trip: Appears when the voltage
Voltage
imbalance value exceeds the set
imbalance
value (default 5%).
Possible failure reasons
Supply voltage is
not
in the
specified range.
Loose wiring connections at the
terminal plate.
Worn out contactors.
Faults
with
other
peripheral
electrical loads.
Loose wiring connections at the
compressor terminal plate inside T-
Box.
Worn out contactors.
Faults
with
other
peripheral
electrical loads.
Single phasing conditions.
Troubleshooting measures
Verify voltage supply from the main buss.
Verify voltage into and out of contactor (repair or replace contactor if necessary).
Measure voltage at the compressor terminal (refer to AE10-1244, Recommended
Contactor Selection for 3-Phase Motor Control – Power Supply Problems).
Verify that motor electrical connections are tight at the compressor.
Verify that there are not any faults with other peripheral electrical loads (for example
fan motors).
Verify voltage supply from the main buss.
Verify voltage into and out of contactor (repair or replace contactor if necessary).
Measure voltage at the compressor terminal (refer to AE10-1244, Recommended
Contactor Selection for 3-Phase Motor Control– Power Supply Problems).
Verify that motor electrical connections are tight at the compressor.
Verify that there are not any faults with other peripheral electrical loads (for example
fan motors).