Carrier 50TFQ008 Installation, Start-Up And Service Instructions Manual page 17

Single-package rooftop heat pump units, 50 hz, ce units
Table of Contents

Advertisement

Table 10 — Fan Performance (SI), 50TFQ008,009 — Horizontal Discharge Units
AIRFLOW
50
(L/s)
R/s
BkW
R/s
1100
7.9 0.35
9.4 0.50 10.6 0.68 11.7 0.85 12.7 1.03 13.6 1.25 14.4 1.46 14.9 1.69 15.1 1.92 15.0 2.15
1200
8.3 0.42
9.8 0.59 11.0 0.78 12.0 0.95 13.0 1.15 13.9 1.36 14.8 1.58 15.5 1.82 16.0 2.06 16.4 2.31
8.8 0.51 10.2 0.69 11.3 0.88 12.4 1.08 13.3 1.28 14.2 1.49 15.0 1.72 15.8 1.96 16.5 2.21 17.1 2.47
1300
1400
9.2 0.60 10.6 0.80 11.7 0.99 12.7 1.22 13.7 1.42 14.5 1.63 15.3 1.87 16.1 2.12 16.9 2.38
1500
9.7 0.71 11.0 0.91 12.1 1.12 13.0 1.35 14.0 1.59 14.8 1.81 15.6 2.04 16.4 2.30
1600
10.1 0.82 11.3 1.04 12.5 1.28 13.4 1.49 14.3 1.75 15.2 2.00 15.9 2.24
1700
10.6 0.93 11.8 1.20 12.9 1.44 13.8 1.67 14.7 1.92 15.5 2.20
LEGEND
BkW — Motor Brake (Output) Power (kW)
R/s
— Fan Wheel Speed, Revolutions per Second
NOTES:
1. Boldface indicates field-supplied drive required.
2.
indicates field-supplied motor and drive required.
3. Maximum usable output power (BkW) is 1.79 with standard
1.12-BkW motor. Extensive motor and electrical testing on these
Table 11 — Fan Performance (SI), 50TFQ012 — Horizontal Discharge Units
AIRFLOW
50
(L/s)
R/s
BkW
R/s
1300
7.6 0.30
8.9 0.41 10.2 0.56 11.1 0.64 12.1 0.77 13.1 0.92 13.9 0.93 14.0 0.52 15.0 1.13 15.6 1.32
1400
8.0 0.40
9.3 0.51 10.5 0.64 11.4 0.75 12.4 0.88 13.3 1.01 14.1 1.11 14.6 0.96 15.4 1.32 16.0 1.42
1500
8.4 0.48
9.6 0.60 10.7 0.72 11.8 0.86 12.7 0.99 13.5 1.12 14.3 1.26 15.1 1.35 15.7 1.49 16.4 1.54
1600
8.8 0.58 10.0 0.69 11.1 0.82 12.1 0.96 12.9 1.10 13.8 1.24 14.5 1.38 15.3 1.54 16.0 1.64 16.7 1.72
1700
9.1 0.69 10.3 0.78 11.3 0.93 12.3 1.07 13.2 1.22 14.0 1.37 14.8 1.52 15.5 1.66 16.3 1.84 17.0 1.95
1800
9.5 0.81 10.7 0.90 11.7 1.05 12.6 1.20 13.5 1.36 14.3 1.52 15.0 1.67 15.8 1.83 16.4 1.99 17.2 2.17
1900
9.9 0.95 11.0 1.02 12.0 1.18 12.9 1.34 13.8 1.50 14.6 1.68 15.3 1.83 16.0 2.00 16.7 2.16 17.3 2.33
2000
10.3 1.11 11.4 1.17 12.3 1.32 13.2 1.48 14.1 1.66 14.9 1.83 15.6 2.01 16.3 2.18 17.0 2.36 17.6 2.53
2100
10.7 1.29 11.8 1.33 12.7 1.47 13.5 1.65 14.4 1.84 15.1 2.00 15.9 2.20 16.6 2.38
2200
11.2 1.48 12.1 1.51 13.1 1.64 13.9 1.83 14.6 2.01 15.4 2.20 16.2 2.38
2300
11.6 1.70 12.5 1.71 13.4 1.83 14.2 2.01 15.0 2.20 15.7 2.41
LEGEND
BkW — Motor Brake (Output) Power (kW)
R/s
— Fan Wheel Speed, Revolutions per Second
NOTES:
1. Boldface indicates field-supplied drive required.
2.
indicates field-supplied motor and drive required.
3. Maximum usable output power (BkW) is 2.16 with standard
1.50-BkW motor. Extensive motor and electrical testing on these
EXTERNAL STATIC PRESSURE (Pa)
100
150
200
BkW
R/s
BkW
R/s
BkW
EXTERNAL STATIC PRESSURE (Pa)
100
150
200
BkW
R/s
BkW
R/s
BkW
250
300
350
R/s
BkW
R/s
BkW
R/s
units ensures that the full brakepower range of the motor can be
utilized with confidence. Using your fan motors up to the brake-
power ratings shown will not result in nuisance tripping or prema-
ture motor failure.
4. Use of field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
5. Values include losses for filters, unit casing, and wet coils.
6. Motor drive range is 10.33 to 14.67 r/s. All other r/s's will require a
field-supplied drive.
250
300
350
R/s
BkW
R/s
BkW
R/s
units ensures that the full brakepower range of the motor can be
utilized with confidence. Using your fan motors up to the brake-
power ratings shown will not result in nuisance tripping or prema-
ture motor failure.
4. Use of field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
5. Values include losses for filters, unit casing, and wet coils.
6. Motor drive range is 11.50 to 15.00 r/s. All other r/s's will require a
field-supplied drive.
17
400
450
BkW
R/s
BkW
R/s
BkW
400
450
BkW
R/s
BkW
R/s
BkW
500
R/s
BkW
500
R/s
BkW