Rs485 Network Connection - Danfoss VLT Decentral Drive FCD 302 Design Manual

Hide thumbs Also See for VLT Decentral Drive FCD 302:
Table of Contents

Advertisement

Application Examples

4.5.2 RS485 Network Connection

FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
RS-485
06
61
+
68
69
-
Table 4.11 RS485 Network Connection
MG04H302
Design Guide
Parameters
Function
Setting
Parameter 8-30 P
[0] FC*
rotocol
Parameter 8-31 A
1*
ddress
Parameter 8-32 B
9600*
aud Rate
*=Default value
Notes/comments:
Select protocol, address, and
baud rate in the above
mentioned parameters.
Danfoss A/S © 05/2018 All rights reserved.
4.5.3 Motor Thermistor
NOTICE
Thermistors must use reinforced or double insulation to
meet insulation requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 4.12 Motor Thermistor
Parameters
Function
Setting
Parameter 1-90
[2] Thermistor
Motor Thermal
trip
Protection
Parameter 1-93 T
[1] Analog
hermistor Source
input 53
*=Default value
Notes/comments:
If only a warning is desired,
parameter 1-90 Motor Thermal
Protection should be set to [1]
Thermistor warning.