6 5 Mounting

6.1 5.1 General

Study these installation instructions carefully before proceeding.
Failure to observe the warnings and instructions may cause a
malfunction or personal hazard. Before installing the field
instrument, check whether the device design meets the
requirements of the measuring point from a measurement
technology and safety point of view. This applies in respect of the:
Explosion protection certification
Temperature
— Operating voltage and current
In addition, the relevant directives, regulations, standards, and
accident prevention regulations must be observed (e.g., VDE/VDI
3512, DIN 19210, VBG, Elex V, etc.). As far as possible, the setup
should be free from critical ambient conditions such as extreme
temperatures, vibrations, or shocks.
Important. If unfavorable ambient conditions cannot be avoided for
reasons relating to building structure, measurement technology, or
other issues, product quality may be affected.
6.2 5.2 IP protection & designation
The housings for JDF200 Field Indicator The field indicator is dust
and sand tight and protected against immersion effect as defined
by IEC60529 to IP67 or by NEMA Type 4X.
The first number indicates the protection of the electronics against
the entry of foreign bodies, including dust.
"6" means that the housing is dust-proof (i.e., no ingress of
dust). The second number indicates the type of protection
the integrated electronics have against the entry of water.
The second number indicates the protection of the electronics
against the entry of foreign bodies, including dust.
"7" means that the housing is protected against water; specifically,
against the effects of temporary immersion in water under
standardized water pressure and temporal conditions.

6.3 5.3 General mounting information

6.3.1 5.3.1 Transmitter factory configuration consideration

The field indicator in your hands has been manufactured to reflect
the published specification. ABB configures JDF200 field indicator
according to the user requirements. A configuration includes:
TAG number
LCD display configuration
— Scaling range

6.3.2 5.3.2 Hazardous area considerations

The field indicator can be installed in hazardous area only if
certified. The certification plate is permanently fixed on the field
indicator housing. JDF200 can have the following certifications:
INTRINSIC SAFETY:
ATEX Europe (code E1) approval
II 1G Ex ia IIC Tx Ga and II 1D Ex ta IIIC Tx Da IP67 and
II 1D Ex ia IIIC Tx Da IP67.
IECEx (code E8) approval
Ex ia IIC Tx Ga and Ex ta IIIC Tx Da IP67 and Ex ia IIIC Tx Da IP67
EXPLOSION PROOF:
ATEX Europe (code E2) approval
II 2G Ex db IIC Tx Gb and II 2D Ex tb IIIC Tx Db IP67
IECEx (code E9) approval
Ex db IIC Tx Gb and Ex tb IIIC Tx Db IP67
Type "n" and Intrinsically safe Ex ic:
ATEX Europe (code E3 ) type examination
II 3G Ex nA IIC Tx Gc and II 3G Ex ic IIC Tx Gc and II 3D Ex tc IIIC
Tx Dc IP67
IECEx (code ER) type examination
Ex nA IIC Tx Gc and Ex ic IIC Tx Gc and Ex tc IIIC Tx Dc IP67
Intertek US (cod. EV) and Intertek Canada (cod. EU):
— Explosionproof
US: Class I, Div. 2, Groups A, B, C, D T6...T4
Class II, Div 2 Groups F, G T6...T4
Class I, Zone 1 AEx d IIC T6...T4 Gb
Class II, Div 1 Groups E, F, G T6...T4, Zone 20 AEx ta IIIC
T85°C...T135°C Da
Canada:
Ex d IIC T6...T4 Gb
Ex tb IIIC T85°C...T135°C Db
Ex ta IIIC Tx Da IP67
— Non-sparking
US: Class I, Zone 2 AEx nA IIC T6...T4 Gc
Class I, Div 2 Groups ABCD T6...T4
Canada:
Ex nA IIC T6...T4 Gc
— Intrinsically safe
US: Class I, Zone 0 AEx ia IIC T6...T4 Ga
Class I, Division 1 Groups A, B, C, D T6...T4
Class II, Division 1 Groups E, F, G T6...T4
When connected per drawing No. DH3260
Class I, Division 2 Groups A, B, C, D T6...T4
Class I, Zone 2 AEx ic IIC T6...T4 Gc
When connected per drawing No. DH3260
Canada:
Ex ia IIC T6...T4 Ga
Ex ia IIIC T85°C...T135°C Da
When connected per drawing No. DH3260
Ex ic IIC T6...T4 Gc
When connected per drawing No. DH3260
— Enclosure type 4X
COMBINED ATEX (cod. EW = E1+E2+E3), (cod. E7 = E1+E2)
COMBINED ATEX, cNRTLus, IECEx Approvals
(cod. E5 = EW+EV+EU+EI)
COMBINED NRTL Approvals US and Canada
— Intrinsically safe (code EJ)
— Explosionproof (code EK)
— Nonincendive (code EL)
COMBINED IECEx (cod. EH = E8+E9), (cod. EI = E8+E9+ER)
6.4 Warning - General risk for JDF200 used in zone
0
Model JDF200 enclosure contains aluminium and is considered to
present a potential risk of ignition by impact or friction. Care must
be taken into account during installation and use to prevent
impact or friction.

6.5 5.4 Mounting JDF200 field indicator

The field indicator model JDF200 can be mounted directly a wall
5 Mounting
2600T Series | OI/JDF200-EN Rev. E 9