12.8 11.8 ETL marking and entities

— Conforms to UL 61010-1, UL 60079-0, UL 60079-1, UL 60079-11, UL 60079-15 and UL 60079-31
— Certified with CSA C22.2.61010-1, CSA C22.2.60079-0, CSA C22.2.60079-11, CSA C22.2.60079-15 and
CSA C22.2.60079-31
ETL approval
Type of protection
CL I, Zone 0 AEx ia IIC T6...T4 Ga
CL I, Div 1 GP ABCD T6...T4
US
CL II, Div 1 GP EFG T6...T4
When connected per DWG DH3260
Ex ia IIC T6...T4 Ga
Canada
Ex ia IIIC T85°C...T135°C Da
When connected per DWG DH3260
CL II, Div 1 GP EFG T6...T4
US*
Zone 20 AEx ta IIIC T85°C...T135°C Da
Canada*
Ex ta IIIC Tx Da IP67
CL I, Div 2 GP ABCD T6...T4
US
CL II, Div 2 GP FG T6...T4
CL I, Zone 1 AEx d IIC T6...T4 Gb
Ex d IIC T6...T4 Gb
Canada
Ex tb IIIC T85°C...T135°C Db
CL I, Zone 2 AEx nA IIC T6...T4 Gc
US
CL I, Div 2 GP ABCD T6...T4
Canada
Ex nA IIC T6...T4 Gc
CL I, Div 2 GP ABCD T6...T4
US
CL I, Zone 2 AEx ic IIC T6...T4 Gc
When connected per DWG DH3260
Ex ic IIC T6...T4 Gc
Canada
When connected per DWG DH3260
*The current limitation is applicable only if the equipment is used only with the Ex ta type of protection (CL II Div 1 GP EFG T6...T4
and Zone 20 AEx ta IIIC T85°C...T135°C Da for US and Ex ta IIIC Tx Da IP67 for Canada)
32 OI/JDF200-EN Rev. E | 2600T Series
11 Requirements for installation and use in US and Canada
T4/T135
T4/T135
-40°C<Ta<+85°C
-40°C<Ta<+70°C
Ui/Vmax= 30 Vdc
Ui/Vmax= 30 Vdc
Ii/Imax= 100 mA
Ii/Imax= 160 mA
Pi/Pmax= 0.75 W
Pi/Pmax= 1 W
-50°C<Ta<+85°C
-50°C<Ta<+70°C
Ui/Vmax = 30Vdc
Ui/Vmax = 30Vdc
Ii/Imax = 58 mA*
Ii/Imax = 95 mA*
-40°C<Ta<+75°C
Ui/Vmax = 42Vdc
N/A
Ii/Imax = 100 mA
-40°C<Ta<+75°C
-40°C<Ta<+70°C
Ui/Vmax = 42Vdc
Ui/Vmax = 30Vdc
Ii/Imax = 100 mA
Ii/Imax = 160 mA
-40°C<Ta<+75°C
-40°C<Ta<+70°C
Ui/Vmax= 42Vdc
Ui/Vmax= 30Vdc
Ii/Imax= 100 mA
Ii/Imax= 160 mA
Pi/Pmax= 1 W
Pi/Pmax= 1 W
T5/T100
T6/T85
-40°C<Ta<+40°C
-40°C<Ta<+40°C
Ui/Vmax= 30 Vdc
Ui/vmax= 30 Vdc
Ii/Imax= 100 mA
Ii/Imax= 50 mA
Pi/Pmax= 1,75 W
Pi/Pmax= 0.4 W
-50°C<Ta<+40°C
-50°C<Ta<+40°C
Ui/Vmax = 30Vdc
Ui/Vmax = 30Vdc
Ii/Imax = 58 mA*
Ii/Imax = 28 mA*
-40°C<Ta<+75°C
-40°C<Ta<+75°C
Ui/Vmax = 42Vdc
Ui/Vmax = 42Vdc
Ii/Imax = 100 mA
Ii/Imax = 100 mA
-40°C<Ta<+40°C
-40°C<Ta<+40°C
Ui/Vmax = 42Vdc
Ui/Vmax = 42Vdc
Ii/Imax =  40 mA
Ii/Imax = 40 mA
-40°C<Ta<+40°C
-40°C<Ta<+40°C
Ui/Vmax= 42Vdc
Ui/Vmax= 42Vdc
Ii/Imax= 40 mA
Ii/Imax= 40 mA
Pi/Pmax= 1 W
Pi/Pmax= 1 W