12.7 11.7 Ex Safety aspects and IP Protection (Canada)

Important. For ambient temperature range from -50°C to -40°C before installation permanentely protect window cover from accidental impact.
12.7.1

12.7.2 11.7.1 Applicable standards

According to Intertek here is the list of Standards which can assure compliance with Essential Safety Requirements
CSA 61010-1
Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, General Requirements
CSA 60079-0: Electrical Equipment for use in Hazardous (Classified) Locations, General Requirements.
CSA 60079-1: Electrical Equipment for use in Hazardous (Classified) Locations, protection by flameproof enclosures "d".
CSA 60079-11: Electrical Equipment for use in Hazardous (Classified) Locations, protection by intrinsic safety "i".
CSA 60079-15: Electrical Equipment for use in Hazardous (Classified) Locations, protection by intrinsic safety "n".
CSA 60079-31 Electrical Equipment for use in Hazardous (Classified) Locations, dust ignition protection by enclosure "t".

12.7.3 11.7.2 Classifications

The field indicator has been certified for the following Class, Divisions and Gas groups, hazardous classified locations, temperature
class and types of protection.
— Explosionproof (Canada) for zone 1 gas, group IIC, hazardous (classified) locations.
— Dust ignition proof for Class II, III Division 1, Groups E, F and G, hazardous (classified) locations, as Ex ta type of protection.
— Suitable for Class II, III, Division 2, Groups F and G, hazardous (classified) locations.
— NonIncendive for Class I, Division 2, Groups A, B, C and D, in accordance with Nonincendive field wiring
requirements for hazardous (classified) locations, as Ex ic type of protection.
— Intrinsically Safe for use in Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G in accordance with Entity
requirements for hazardous (classified) locations.
— Temperature class T4 to T6 (dependent on the maximum input current and the maximum ambient temperature).See table
at paraghraph 11.8 for reference.
— Ambient Temperature range -40°C to +85°C (dependent on the maximum input current and the maximum temperature
class), and -50°C to +85°C when protected by impact because the impact test was made at 2J.
— Electrical Supply range Minimum 4 mA, Maximum 20 mA.
— Type 4X applications Indoors/Outdoors.
For a correct installation in field of JDF200 field indicator please see the related control drawing No DH3260

12.7.4 11.7.3 Special conditions

Installation cables suitable dor specific maximum temperature are indicated in the table here below:
The ambient temperature is not indicated on the label but on this user manual.
The enclosure can be made in aluminium. The installation of the equipment must take this into account with respect of impact and
friction sparking for it to be suitable dor Group II fro EPL Ga. That is not indicated on the label but only in this user manual.
The final user can chose the level of protection of the equipment when the equipment is with the option E5, EJ, EK or EL on the
type of code for Hazardous areas certifications. When the selection is made, it is not possible to change it. The same procedure
has to applied for all the other codes when it is present a multiple choice for the type of protection.
Important. When installed with a conduit, a seal shall be installed within 50mm of the enclosure.
11 Requirements for installation and use in US and Canada