L3, Indoor unit.
Indoor Standby LED, flashing 23 times.
Red LED, Outdoor unit flashing 14 times.
(Outdoor DC Fan Motor Malfunction)
# Check the condenser fan for correct operation. If the fan motor is not operating check the three pin
DC-Motor connector plug for correct termination to the outdoor PCB.
# With the unit set in heating or cooling mode (depending on ambient conditions) Check for DC voltage
from the points illustrated below, located on the main outdoor PCB.
Red & Yellow wires: < 13 Volts DC.
Red & White wires: < 13 Volts DC.
Red, Yellow & White wires on three pin outdoor DC-Motor
connector plug.
Page 25 KSSSI113